Installation
3-20
TIWAY 1 TI505 NIM User Manual
If
the NIM fails the test, the following conditions apply
.
1. If
the NIM GOOD LED indicator is extinguished, then an internal NIM
failure
was
detected.
2. If
the PC GOOD LED indicator is extinguished, then a problem was found in at
-
tempting
to communicate with a TI505 P/C.
3. If
the XMT LED indicator is extinguished, a failure was detected on the bottom
port
(Port B). This could be due to a missing loopback connector
.
4. If
the RCV LED indicator is extinguished, a failure was
detected on the
top
network port (Port A). This could be due
to a missing loopback con
-
nector.
Following successful execution of the diagnostics, the network cable(s) should be
connected to the NIM, the NIM Reset button should be pressed and the
LOCAL/REMOTE
switch should be returned to the
correct setting (for your application).
This
will reinitialize the NIM, and it will return to normal operation.
If you need additional help, or information that is not included in this Technical
Advisory,
contact your Siemens Industrial
Automation, Inc. distributor or sales agent. If
you need assistance in contacting your distributor or sales office in the United States,
call 800–964–4114. If additional technical assistance is needed, call the SIA Technical
Services
Group in Johnson City
, T
ennessee at 615–461–2522.