Network Design Considerations
2-11
TIWAY 1 Ti505 NIM User Manual
With
the cover removed from the PPX:500–5606 T
ap Housing,
note that there are three
sets of terminals, and that each set is labeled G (Ground), W (White), and B (Blue). (See
Figure
2Figure 2.) One set of these terminals is for the incoming Local Line twisted pair;
the
center set is for the drop line; and the remaining set is used to connect the Local
Line
to
the following node, or to terminate the Local Line if the tap housing is the last one on
the
network trunk.
For
consistency in installation, always connect the LLM+ (Pin 6 of the Local Line Con
-
nector)
to the white strand of the twisted pair and to the terminal marked “W”
in the tap
housing. Connect the blue strand to the LLM– (Pin 9 of the Local Line Connector) and to
the terminal marked “B” in the tap housing. The Cable Shield and Signal Common
should
be connected to Pin 3 of the Local Line
connector and to terminal “G” inside the
tap
housing.
NOTE
All Siemens tap housings contain factory-installed termination
resistors.
If the tap housing is not used to terminate the
Local Line, the
terminating resistors must be removed when the output cable is
attached.