6.5.5 Blind start of scale value/full scale value
6.5.5.1
Difference between setting/adjusting and blind setting/adjusting
Differences
In contrast to setting/adjusting with a reference pressure, you do not need a reference pressure
for blind setting/adjusting. You can adjust a value in the physical variable "pressure" without
a reference pressure, and an output current with a reference pressure.
Blind adjusting
First select the desired physical unit. Then, adjust two pressure values using the [↑] and [↓]
buttons and save them in the device. These theoretical pressure values are allocated to the
standard current values 4 mA and 20 mA.
Depending on the series and measuring range, a maximum downscaling of 1:100 can be
achieved (measuring span ratio = r, turn down).
The correlation between the measured pressure and the output current generated is linear.
The square root extracting characteristic curve for differential pressure transmitters is an
exception.
Example of blind adjusting
A Initial situation
0$
DFWXDO
0$
WDUJHW
0(
DFWXDO
0$
DFWXDO
0$
WDUJHW
0(
WDUJHW
S>EDU@
,>P$@
S>EDU@
,>P$@
S>EDU@
,>P$@


 


 

B Blind adjustment of the start of
scale value
C Blind adjustment of the full
scale value
I Output current p Pressure
MA
actua
l
Old start of scale value MA
target
New start of scale value
ME
actua
l
Old full scale value ME
target
New full scale value
Operation
6.5 Local operation
SITRANS P, DS III series with HART
Operating Instructions, 09/2012, A5E00047092-08 83