Installation type J
Between the measuring points, no
vacuum
H
2
≤ 7 m (23 ft); with halocarbon oil as the filling
liquid, only H
2
≤ 4 m(13.1 ft)
Start of scale value:
p
MA
= ρ
FL
* g * H
U
- ρ
oil
* g * H
V
Full-scale value:
p
ME
= ρ
FL
* g * H
O
- ρ
oil
* g * H
V
Key
p
MA
Start of scale value
p
ME
Full-scale value
ρ
FL
Density of the process medium in the container
ρ
oil
Density of the filling oil in the capillary line of the remote seal
g Acceleration due to gravity
H
U
Lower filling level
H
O
Upper filling level
H
V
Gland distance
4.6 Turing the measuring cell against housing
Description
You can turn the measuring cell against the housing. Turning simplifies the transmitter
operation in the case of an angled installation environment. The buttons and the current
connection can thus also be operated for an external measuring device. The display also
remains visible in enclosure covers with an inspection window.
Only limited turning is permissible! The turning range ① is marked at the foot of the electronic
housing. An orientation mark ③ is provided at the throat of the measuring cell. This mark must
remain in the marked section when turning.
Installing/mounting
4.6 Turing the measuring cell against housing
SITRANS P, DS III series with HART
54 Operating Instructions, 09/2012, A5E00047092-08