3.6.3.4 Measuring cell for absolute pressure from the differential pressure series
S
H

Pressure cap Overload diaphragm
Seal diaphragm on the measuring cell Measuring cell filling liquid
O-ring Reference pressure
Measuring cell body p
e
Pressure input variable
Absolute pressure sensor
Figure 3-10 Function chart of measuring cell for absolute pressure
Absolute pressure is transmitted to the absolute pressure sensor through the seal
diaphragm and the filling liquid .
When measuring limits are exceeded, the overload diaphragm is displaced until the seal
diaphragm rests on the measuring cell body . The seal diaphragm thus protects the
absolute pressure sensor from overload.
The difference between the inlet pressure (p
e
) and the reference pressure on the
negative side of the measuring cell displaces the seal diaphragm . The displacement
changes the resistance of the four piezoresistors (bridge circuit) of the absolute pressure
sensor.
Description
3.6 Functional principle
SITRANS P, DS III series with HART
28 Operating Instructions, 09/2012, A5E00047092-08