ST800 Guidance Notes
Issue 1 667/HB/27000/100 Page 9
Checks that each lamp supply relay can switch off the lamp supply independantly
SSR Fault
Relay A Fault
Relay B Fault
Failure of any of these tests implies that the relay is not switching off, i.e. that
it is either welded closed or the control signals from the main processor card
are stuck active.
Checks that the dimming relay is functioning
Dimming Fault
A fault is only logged on the dimming relay if the dim lamp supply is more
than 75% of the normal lamp supply, i.e. that the dimming relay seems to
have no effect on the lamp supply. If dimming is not required, then no link
should be fitted between the dim input and the dim output on the back of the
distribution unit. If dimming is configured as not present, i.e. KDP is set to
zero, then the controller will simply never attempt to switch to dim.
Note that this test does not fail if there is no dim lamp supply, e.g. if no
dimming transformer is fitted, since self test may be performed on the just the
controller rack. Therefore, the dim voltage should be checked manually, e.g.
Dim L/Supply=160V
Checks all of the triacs in turn by applying a very short pulse to each phase’s colour
A/Red:Extra Sigs On
R-00000001+00000001
A-00000001+00000001
G-00000001+00000001
A fault will be logged if extra signals are detected as on when one particular
aspect is pulsed. This would normally imply a short-circuit in the street cabling
or a open neutral connection.
No Voltages On...
R-00000F00+00000F00
A-00000F00+00000F00
G-00000F00+00000F00
A fault will also be logged if no voltages were detected, e.g. when one of the
fuses on one of the lamp switch cards has blown.
At the end of the test, the self test switches off the lamp supply and displays a
multicoloured scrolling pattern on the lamp switch card LED's to show that all the
tests have passed successfully.
It also illuminates a series of amber LED's to identify which cards on the extended
system bus have been detected. A full list is displayed on the handset.
After a few seconds, self test will repeat the tests on these last two pages allowing
the controller to be soak tested.