SIEMENS TRAFFIC CONTROLS LIMITED 667/HB/27000/100Sopers LanePOOLE Dorset.BH17 7ERSYSTEM/PROJECT/PRODUCT: ST800SIEMENS TYPE 800TRAFFIC CONTRO
ST800 Guidance NotesPage 10 667/HB/27000/100 Issue 1Handset IntroductionUnlike the T400, no prompt is automatically displayed when the handset is firs
ST800 Guidance NotesIssue 1 667/HB/27000/100 Page 11Fault LogThe ST800 uses the same fault log commands as on the T400. Therefore to displaythe curren
ST800 Guidance NotesPage 12 667/HB/27000/100 Issue 1FLF ABBR FLD Description0 - Not Used1 - Not Used2PBUS10-12 Phase Bus Processor Checks FailFault lo
ST800 Guidance NotesIssue 1 667/HB/27000/100 Page 13FLF ABBR FLD Description4RLAY3 Relay Tests Failed:The relay tests try to detect short-circuits whi
ST800 Guidance NotesPage 14 667/HB/27000/100 Issue 1FLF ABBR FLD Description11 MEM5 Memory Fault:The allocation of the fault data will change:FLD 5:00
ST800 Guidance NotesIssue 1 667/HB/27000/100 Page 15FLF ABBR FLD Description27SCF118 Special Conditioning - General Fault 128SCF219 Special Conditioni
ST800 Guidance NotesPage 16 667/HB/27000/100 Issue 1Lamp MonitoringLamp monitoring is now performed internally by the controller’s main processor, noo
ST800 Guidance NotesIssue 1 667/HB/27000/100 Page 17When learning is complete, the learnt load for each sensor and aspect, i.e. eachphase and colour,
ST800 FAULT REPORT CHECK LISTPage 1 667/HB/27000/100 Issue 1Visit InformationSite name: Date / Time: / / :Engineer’s name: Telephone:Reason for visit:
ST800 Guidance NotesPage 2 667/HB/27000/100 Issue 1IntroductionThe following pages summarize how to use the new ST800 traffic controller fromSiemens.
ST800 FAULT REPORT CHECK LISTIssue 1 667/HB/27000/100 Page 2Serial NumbersIf the controller’s power needs to be switched off in order to fix/clear the
ST800 Guidance NotesIssue 1 667/HB/27000/100 Page 3ConnectionsThe following diagrams detail the connections on the back of the power distributionunit
ST800 Guidance NotesPage 4 667/HB/27000/100 Issue 1The following diagram shows the connections in the power connector on the back ofthe main processor
ST800 Guidance NotesIssue 1 667/HB/27000/100 Page 5Self TestThe self test facility can be used to check the hardware fitted to the controller, evenwit
ST800 Guidance NotesPage 6 667/HB/27000/100 Issue 1On power-up, the self test facility...Checks the integrity of the main processor boardRAM FAULTPRG
ST800 Guidance NotesIssue 1 667/HB/27000/100 Page 7Checks that the lamp supply and voltage monitors are detecting no mainsL/Supply Off=240VL/Supply St
ST800 Guidance NotesPage 8 667/HB/27000/100 Issue 1After the level 3 button is pressed, self test switches on the lamp supply.Towards the end of this
ST800 Guidance NotesIssue 1 667/HB/27000/100 Page 9Checks that each lamp supply relay can switch off the lamp supply independantlySSR FaultRelay A Fau