ST800 Guidance Notes
Page 16 667/HB/27000/100 Issue 1
Lamp Monitoring
Lamp monitoring is now performed internally by the controller’s main processor, no
other cards are required and very little, if any external wiring is required.
The lamp monitor is automatically configured from the configuration PROM and will
be ready to learn the lamps of the junction.
Should the lamp monitor need resetting explicitly, then ‘KLR=1’ should be entered.
Before leaving a controller, the lamp monitor should be checked to ensure that it has
learnt the junction, i.e. that it has been given time to confirm exactly how much
current flows for each phase and colour.
This can be achieved by entering ‘KML. This command automatically cycles
through all the phases and colours which the lamp monitor has not yet learnt,
resulting in displays of the following format:-
KML:LMU Disabled
Lamp monitoring has not been enabled in the configuration.
KML:A/Red 0%
Phase A red is 0% learnt, i.e. the lamp monitor has not
seen phase A red illuminated.
KML:A/Green 50%
Phase A green is 50% learnt, i.e. the lamp monitor has
learnt in the current in either dim or bright but learning is not
complete until the lamp monitor has learnt the current in
both states.
KML:A/Amber 25%
Phase A amber is 25% learnt, i.e. the lamp monitor has
started to learn the current but the colour has not yet been
illuminated for long enough.
KML:Awaiting D/B
The lamp monitor has finished learning all the currents in
the present dim or bright state and is waiting for a change to
the other state in order to complete the learning process.
KML:A/Red 100%
The lamp monitor has completely learnt phase A red.
KML:S33/A1 0%
The external optional sensor number 33, aspect pattern 1
has not yet been learnt. Most configurations will be
defaulted to provide two spare sensors which can be used
to monitor regulatory signs. If no signs are fitted, then the
lamp monitor will happily learn zero current when the
signals are bright after a short delay.
KML:Complete
Learning is complete, i.e. the lamp monitor has successfully
learnt all of the currents of the junction.