Distributed Use of SIMATIC FS600 Laser
Scanner in Category 3 / SIL 2
Entry ID: 21330889
A&D Safety Integrated Page 9/51 AS-FE-I-010-V20-EN
Copyright © Siemens AG 2007 All rights reserved
21330889_as_fe_i_010_v20_en_lscanner.doc
2.1.2 Functionality of the safety functional example
The STEP 7 project (hardware configuration and sample code) to the safety
functional example comprises the following components:
fail-safe S7-CPU (DP master)
laser scanner SIMATIC FS600 for PROFIBUS (DP slave)
standard and fail-safe input and output modules of ET 200S (DP slave)
In the safety functional example, a hazardous machine is simulated by an
indicator light (actuator) which is connected to a fail-safe digital output
module (F-DO). The term "machine" will be used to designate the indicator
light (actuator) in the following.
If the active detection zone of the laser scanner SIMATIC FS600 is violated
while the “machine” is switched on, the “machine” will be switched off
automatically (indicator light off). Restarting the “machine” is only possible if
an acknowledgement is given first.
The status of the sensors defines the detection zone numbers (bits 0, 1 and
2 of the cyclic output data). It defines which protection and warning zone is
active. In the safety functional example, either zone pair 1 (detection zone 1
and warning zone 1) or zone pair 2 (detection zone 2 and warning zone 2)
is active. If you want to expand the safety functional example with the aim
to work with three or four zone pairs, you can use the prepared program
sequences of the sample code (further information given in chapter 6).
The sensors for switching the detection zones are directed to a fail-safe
input module of the (F-DI). If this F-DI malfunctions, switching between the
detection zones is not possible anymore. This fault is recognized. As a
response to this fault, the fail-safe output module (F-DO) is set to fail-safe
mode (indicator light switched off).
NOTICE
In order to meet the requirements of category 3 / SIL 2, it is
obligatory for certain actuators (e.g. contactor) to read back the
process signal to the actuator.
Read-back is not implemented in this safety functional example. The
actuator is an indicator light simulating a machine. When using
different actuators, the feedback circuits have to be integrated and
evaluated by the user. Safety functional example 7 provides a
detailed description of “Read back”.