
Distributed Use of SIMATIC FS600 Laser Scanner in
Category 3 / SIL 2
Entry ID: 21330889
A&D Safety Integrated Page 38/51 AS-FE-I-010-V20-EN
Copyright © Siemens AG 2007 All rights reserved
21330889_as_fe_i_010_v20_en_lscanner.doc
Network 2
In OB1 the “Proxy-Enable“ bit (Bit 6 of the cyclic output data) is
permanently supplied with the value “0“.
Network 3
The laser scanner SIMATIC FS600 can be parameterized automatically
when it is replaced. This is prepared in network 3 by calling “FB LS4”. But
the automatic parameter configuration is not effective since the Proxy-
Enable bit permanently has the value “0”.
To use the automatic parameter configuration, you must set the Proxy-
Enable bit permanently to the value “1” before calling the “FB LS4”.
6.3 Program execution safety program
Structure
The safety program has the following structure:
F-CALL (FC1)
F-CALL (FC1) is the F runtime group and is called from the cyclic interrupt
OB (OB35).
F-CALL (FC1) calls the F program block (here: FC2).
FC FMAIN (FC2)
For modularity reasons of the application program, all further fail-safe
blocks are called from here.
Comentarios a estos manuales