Distributed Use of SIMATIC FS600 Laser
Scanner in Category 3 / SIL 2
Entry ID: 21330889
A&D Safety Integrated Page 17/51 AS-FE-I-010-V20-EN
Copyright © Siemens AG 2007 All rights reserved
21330889_as_fe_i_010_v20_en_lscanner.doc
4.2 Wiring of hardware components
Requirements: The power supply is supplied with 230V AC.
First check the addresses set at the hardware components listed below:
Hardware
component
Address
to be set
Explanation/notes
IM 151 HF 6 (PROFIBUS address) Can be changed
laser scanner
SIMATIC FS600
4 (PROFIBUS address) Default setting, can be changed
F-DI
Switch position:
1111111110
F-DO
Switch position:
1111111101
The PROFIsafe addresses are automatically
assigned when configuring the fail-safe modules
in STEP 7.
The PROFIsafe addresses 1 to 1022 are
permissible. Please make sure that the setting at
the address switch (DIL switch) on the side of the
module corresponds to the PROFIsafe address in
the hardware configuration of STEP7.
Note
The laser scanner SIMATIC FS600 is not illustrated in the picture below.
Its connections will be discussed separately later on.
Note
The DP interface of the CPU 315F-2DP must be connected to the DP
interface of the IM 151 HF and to the laser scanner SIMATIC FS600.