Siemens ET8 Series Instrucciones de operaciones Pagina 50

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 52
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 49
Additional Information CLV61x Dual Port (PROFINET IO)
8017978 / 2014-11-20 © SICK AG · Germany · All rights reserved · Subject to change without notice 50
7.14 Notes regarding operation on other PROFINET IO controllers
If the CLV61x Dual Port is operated on a different controller to an S7, for which no ready-made function
block is available, we recommend the following procedure:
- To begin, set No Handshake.
- Set triggering to fieldbus input or slow (e.g., 5 sec.) auto cycle and only examine the data receipt
at first.
- Use Hex representation for the first 10 input bytes: Can the Heartbeat bit be identified? Can the data
be identified according to chapter 5.2.3., Example 5, receive telegram (NH mode)?
Check the representation of bytes per integer/value variable. Byte order?
- Then, if necessary, switch to Handshake mode and different triggering, e.g., trigger via command.
Vista de pagina 49
1 2 ... 45 46 47 48 49 50 51 52

Comentarios a estos manuales

Sin comentarios