Additional Information CLV61x Dual Port (PROFINET IO)
8017978 / 2014-11-20 © SICK AG · Germany · All rights reserved · Subject to change without notice 26
Time 7: The PLC confirms receipt of the data with ReceiveCountBack = 3.
The TransmitCount must begin again with 1 when 255 is reached, i.e., 0 must be omitted.
The transportable data volume depends on the output range selected.
Output size minus 5 Output block size
The max. length of a data telegram is 4000 bytes divided into several blocks.
5.1.9 Binary status bits In
The first input byte (see chapter 5.1.2) displays the binary status bits In.
It contains some status bits and one heartbeat bit.
Bit Name Meaning
D7
Reserved
D6
Transmit Buffer
Overrun
0: No error
1: The CLV61x Dual Port has received send data from the PLC and the
queue is full.
Reset: With the next successful transmit telegram sent from the PLC.
D5
Receive Buffer
Overrun
0: No error
1: The receive buffer is full and the received data must be discarded.
Reset: With the next modified ReceiveCountBack from the PLC side.
D4
Reserved
D3
PLC Error
0: No error
1: The CLV61x Dual Port identified a handling error when sending data in
the PROFINET IO controller (PLC). The fieldbus module does not accept the
transmitted data if this error occurs and requires
resynchronization with the PROFINET IO controller (PLC). The PLC program
must be corrected based on the error.
Possible causes:
- Impermissible length (e.g., length > 4000).
- The subsequent block was not received within 10 seconds.
- TransmitCount was incremented in the wrong sequence.
If "PLC Error" bit is set, no send data are transmitted.
However, the receiver side is further processed.
If "PLC Error" bit is set, TransmitCountBack is set to 0.
The PLC Error bit is cleared
after TransmitCount is reset to 0 by the PLC.
D2
Heartbeat
0/1: Changes every second shows the presence of the CLV61x Dual Port.
D1
Reserved
D0
Reserved
"Binary Status Bits" - Assignment in Handshake / No-Handshake mode