04/04 Maintenance and Servicing
SINAMICS G130 - Operator Panel AOP30
Operating Manual
6-33
6.2 Load the New Operator Panel Firmware and Database
from the PC.
Description
You have to load the database for the operator panel each time you require a
language other than that stored in the operator panel, or if the chassis unit firmware
has been upgraded to a new version to improve performance or rectify problems.
The load program LOAD_AOP30 and the database files can be found on the CD.
Procedure for Loading the Database
1. Establish the RS232 connection from the PC to the AOP30.
2. Connect the 24 V power supply.
3. Start the LOAD_AOP30 program on the PC.
4. Choose the PC interface (COM1, COM2).
5. Depending on the language you require, choose a file (e.g.
AOP30_DB.V02.10.36.V01.03.02.E.D.CBIN) and open it to start loading the
database.
6. Once the firmware has been loaded, "Database loaded" is displayed on the
AOP30.
7. Switch the power on (switch the power supply off and then back on).
Procedure for Loading Firmware and the Database
1. Establish the RS232 connection from the PC to the AOP30.
2. Connect the 24 V power supply.
3. Start the LOAD_AOP30 program on the PC.
4. Choose the PC interface (COM1, COM2).
5. Choose and open the firmware (AOP30.H86).
6. Follow the instructions in the status window of the program and connect the
power supply for the AOP30 while pressing the red key (O).
7. The load procedure is started automatically.
8. If a current database has not been loaded, the system switches to the "loading
database" screen once the loading procedure has finished
9. Depending on the language you require, choose a file (e.g.
AOP30_DB.V02.10.36.V01.03.02.E.D.CBIN) and open it to start loading the
database.
10. Once the firmware has been loaded, "Database loaded" is displayed on the
AOP30.
11. Switch the power on (switch the power supply off and then back on).