04/04 Control via the Operator Panel
SINAMICS G130 - Operator Panel AOP30
Operating Manual
5-19
Signal Parameters Short name Unit Scaling
(100 % = ...), see Table
5-2
Field-producing current component r0029 A p2002
Torque-producing current component r0030 A p2002
Converter overload
Degree of thermal overload
r0036 % 100 % = Shutdown
Speed setpoint after filter r0062 N_ACT 1/min p2000
Actual speed smoothed r0063 N_ACT 1/min p2000
Control deviation r0064 1/min p2000
Slip frequency r0065 Hz Reference frequency
Output frequency r0066 Hz Reference frequency
Output voltage r0072 UACT V p2001
Control factor r0074 % Reference control factor
Torque-generating actual current r0078 A p2002
Actual torque value r0080 Nm p2003
For further diagnostic purposes
Fixed speed setpoint effective r1024 1/min p2000
Active motor potentiometer setpoint r1050 1/min p2000
Resulting speed setpoint r1119 1/min p2000
Speed controller output r1508 Nm p2003
I component of speed controller r1482 Nm p2003
PROFIBUS setpoint r2050 1/min p2000
Analog input 0 [V, mA] r4052[0] V, mA V: 100 V / mA: 100 mA
Analog input 1 [V, mA] r4052[1] V, mA V: 100 V / mA: 100 mA
Analog input 0, scaled r4055[0] % V: 100 V / mA: 100 mA
Analog input 1, scaled r4055[1] % V: 100 V / mA: 100 mA
Scalings for Vector Object
Table 5-2 Scalings for vector object
Variable Scaling parameter Default for quick commissioning
Reference speed 100 % = p2000 p2000 = Maximum speed (p1082)
Reference voltage 100 % = p2001 p2001 = 1000 V
Reference current 100 % = p2002 p2002 = Current limit (p0640)
Reference torque 100 % = p2003 p2003 = 2 x rated motor torque
Reference power 100 % = r2004
30
πp2000p2003
r2004
××
=
Reference frequency
60
p2000
% 100 =
Reference control factor 100 % = Maximum output voltage
without overload
Reference flux 100 % = Rated motor flux
Reference temperature 100% = 100 °C