04/04 Control via the Operator Panel
SINAMICS G130 - Operator Panel AOP30
Operating Manual
5-23
5.7.2 ON Key/OFF Key
ON key: always active in LOCAL when the operator input inhibit is deactivated.
OFF key: in the factory setting, acts as OFF1 = ramp-down at the deceleration
ramp (p1121); when n = 0: voltage disconnection (only if a main contactor is
installed).
The OFF key is only active in LOCAL mode.
Settings: Menu: Commissioning / Service – AOP Settings – Control Settings
Red OFF key acts as: (factory setting: OFF1)
• OFF1: Ramp-down on the deceleration ramp (p1121)
• OFF2: Immediate pulse block, motor coasts to a standstill
• OFF3: Ramp-down on the emergency stop ramp (p1135)
5.7.3 Switching Between Clockwise and Counter-Clockwise Rotation
Settings: Menu: Commissioning / Service – AOP Settings – Control Settings
Switching between CW/CCW (factory setting: no)
• Yes: Switching between CW/CCW rotation by means of the CW/CCW key
possible in LOCAL mode
• No: The CW/CCW key has no effect in LOCAL mode
For safety reasons, the CW/CCW key is disabled in the factory setting (pumps and
fans must normally only be operated in one direction).
In the operation status in LOCAL mode, the current direction of rotation is indicated
by an arrow next to the operating mode.
NOTE
You have to make additional settings when switching between CW/CCW rotation.