Siemens EF 7850 Series Especificaciones Pagina 31

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 38
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 30
04/04 Control via the Operator Panel
SINAMICS G130 - Operator Panel AOP30
Operating Manual
5-29
Current fault in: 33463512
F7011 Drv: Motor Overtemp.
Help Old Back Ack.
F2F1 F3 F4 F5
Drv: Motor Overtemp.
Fault value: 00000000 00000000H
Cause:
Motor temperature has reached the
fault threshold parameterized in
(p0605).
Remedy:
Back
F2F1 F3 F4 F5
F1
Fig. 5-5 Fault screen
You can use F5 Ack. to acknowledge a stored fault.
Alarm memory Status
A7850 External warning 1
A7910 Drv: Motor Overtemp. active
A7852 External warning 3
Help Delete Back upd.
F2F1 F3 F4 F5
Drv: Motor Overtemp.
AlarmVal: 00000000 00000000(hex)
Cause:
Motor temperature has exceeded the
alarm threshold parameterized in
p0604.
The reaction set in p0610 is
Back
F2F1 F3 F4 F5
F1
F5
Fig. 5-6 Alarm screen
Vista de pagina 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 37 38

Comentarios a estos manuales

Sin comentarios