Control via the Operator Panel 04/04
SINAMICS G130 - Operator Panel AOP30
5-24 Operating Manual
5.7.4 Jog (Reserved for Future Use)
5.7.5 Increase Setpoint / Decrease Setpoint
You can use the “increase” and “decrease” keys to set the setpoint with a
resolution of 1 % of the maximum speed.
(e.g. if the resolution is 15 min
-1
at p1082 = 1500 min
-1
)
You can also enter the setpoint numerically. To do so, press F2 in the operation
screen. The system displays an inverted edit field for entering the required speed.
Enter the required value using the numeric keypad. Press F5 OK to confirm the
setpoint.
When you enter values numerically, you can enter any speed between the
minimum speed (p1080) and the maximum speed (p1082).
Setpoint entry in LOCAL mode is unipolar. You can change the direction of rotation
by pressing the
key (see ).
CW rotation and "Increase key" mean:
The displayed setpoint is positive and the output frequency is increased.
CCW rotation and "Increase key" mean:
The displayed setpoint is negative and the output frequency is increased.