04/04 Connection
SINAMICS G130 - Operator Panel AOP30
Operating Manual
4-11
X540: Serial Interface (RS232)
Table 4-2 Serial interface (RS232) X540
Pin Designation Technical specifications
2 RxD Receive data
3 TxD Transmit data
5 Ground Ground reference
Plug type: 9-pin SUB-D female
NOTE
The maximum cable length is 10 m.
To ensure noise-free communication, you are advised to use a shielded cable and
connect the cable shield to both connector housings.
CAUTION
On the operator panel electronics, a connected cable shield is connected to the
signal and P24 ground. If the power supply is connected with incorrect polarity, the
P24 supply via the shield and signal ground will short-circuit.
Connection
The AOP30 is connected as follows:
1. Connect the power supply cable to the interface for the electronics power
supply (X524).
2. Connect the standard cable to the serial RS232 interface (X540).