SINAMICS G120
Inverter chassis units 0.37 kW to 132 kW (0.5 hp to 200 hp)
PM250 Power Modules
3/44
Siemens D 11.1 · 2008
3
Technical specifications (continued)
Line voltage
380 ... 480 V 3 AC
PM250 Power Modules
With integrated line filter 6SL3225-0BE25-5AA0 6SL3225-0BE27-5AA0 6SL3225-0BE31-1AA0
Output current at 400 V 3 AC
• Rated current I
rated
1)
A 18 25 32
• Base load current
I
L
1)
A 18 25 32
• Base load current
I
H
2)
A 13.2 19 26
I
max
A 26.4 38 52
Rated power
• based on I
L
kW (hp) 7.5 (10) 11 (15) 15 (20)
• based on
I
H
kW (hp) 5.5 (7.5) 7.5 (10) 11 (15)
Rated pulse frequency kW
4 4 4
Efficiency
!
0.95 0.95 0.95
Power loss kW
Available soon Available soon Available soon
Cooling air requirement m
3
/s 0.038 0.038 0.038
Sound pressure level
L
pA
(1 m)
dB
Available soon Available soon Available soon
24 V DC power supply for the
Control Unit
A
1 1 1
Input current
3)
• Rated current
3)
A 18 25 32
• Current based on
I
H
3)
A 13.2 19 26
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals Screw terminals Screw terminals
• Conductor cross-section mm
2
2.5 … 10 2.5 … 10 2.5 … 10
Motor connection
U2, V2, W2
Screw terminals Screw terminals Screw terminals
• Conductor cross-section mm
2
2.5 … 10 2.5 … 10 2.5 … 10
PE connection
On housing with M5 screw On housing with M5 screw On housing with M5 screw
Motor cable length, max.
• Shielded m 25 25 25
• Unshielded m
100 100 100
Degree of protection
IP20 IP20 IP20
Dimensions
• Width mm 189 189 189
• Height mm
334 334 334
• Depth
- without Control Unit mm 185 185 185
- with Control Unit mm
250 250 250
Frame size
FSC FSC FSC
Weight, approx. kg
7.5 7.5 7.5
1)
The rated output current I
rated
and the base load current
I
L
are based on
the loading for light overload (LO).
2)
The base load current
I
H
is based on the loading for high overload (HO).
3)
The input current depends on the motor load and line impedance. It
applies with a line impedance of
u
K
= 1 %. The rated input currents apply
for a load representing the rated power (based on
I
rated
) – these current
values are specified on the rating plate.