SINAMICS G120
Inverter chassis units 0.37 kW to 132 kW (0.5 hp to 200 hp)
PM240 Power Modules
3/34
Siemens D 11.1 · 2008
3
■
Dimensional drawings
PM240 Power Module frame size FSA
Fixing with 2 M4 studs, 2 M4 nuts, 2 M4 washers
Ventilation clearance required at top and bottom:
100 mm
(3.94 inches)
Ventilation clearance required at sides:
Ambient temperature " 40 °C: 0 mm
(0 inches)
Ambient temperature > 40 °C: 30 mm (1.18 inches)
When the Control Unit is plugged in, the mounting depth in-
creases by 65 mm
(2.56 inches) and the total height by 14 mm
(0.55 inches).
Exception
: Mounting depth on CU240E +39 mm (+1.54 inches),
total height +32 mm
(+1.26 inches).
All dimensions in mm
(values in brackets are in inches).
PM240 Power Module frame size FSB
Fixing with 4 M4 studs, 4 M4 nuts, 4 M4 washers
Ventilation clearance required at top and bottom:
100 mm
(3.94 inches)
Ventilation clearance required at sides:
Ambient temperature " 40 °C: 0 mm
(0 inches)
Ambient temperature > 40 °C: 40 mm (1.57 inches)
When the Control Unit is plugged in, the mounting depth in-
creases by 65 mm
(2.56 inches).
Exception
: Mounting depth on CU240E +39 mm (+1.54 inches).
All dimensions in mm
(values in brackets are in inches).
Drill
pattern
G_D011_EN_00091
4.5
(0.18)
145 (5.71) 73 (2.87)
173 (6.81)
160 (6.3)
Drill pattern
G_D011_EN_00092
133
(5.24)
4.8 (0.19)
165 (6.5) 153 (6.02)
270 (10.63)
258 (10.16)
Comentarios a estos manuales