Siemens CU240S DP Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 82
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
SINAMICS G120
Inverter chassis units 0.37 kW to 132 kW (0.5 hp to 200 hp)
CU240 Control Units
3/12
Siemens D 11.1 · 2008
3
Design
Control Unit CU240E
CU240E Control Unit without terminal cover
Terminal No. Signal Features
Digital inputs (DI)
5 … 8,
16,17
DI0 … DI5 Freely programmable (isolated)
5,5 mA/24 V
Digital outputs (DO)
18 DO0, NC Relay output 1
NC contact (0.5 A, 30 V DC)
19
DO0, NO Relay output 1
NO contact (0.5 A, 30 V DC)
20
DO0, COM Relay output 1
Common contact (0.5 A, 30 V DC)
21
DO1, NO Relay output 2
NO contact (0.5 A, 30 V DC)
22
DO1, COM Relay output 2
Common contact (0.5 A, 30 V DC)
23
DO2, NC Relay output 3
NC contact (0.5 A, 30 V DC)
24
DO2, NO Relay output 3
NO contact (0.5 A, 30 V DC)
25
DO2, COM Relay output 3
Common contact (0.5 A, 30 V DC)
Analog inputs (AI)
3 AI0+ 0 … 10 V, –10 … +10 V, 0/2 … 10 V or
0/4 … 20 mA
4
AI0–
10
AI1+ 0 … 10 V, 0 … 20 mA
11
AI1–
Analog outputs (AO)
12 AO0+ Freely programmable (0/4 ... 20 mA with
max. 500 , 0/2 ... 10 V with min. 500 )
13
AO0– M (GND)
26
AO1+ Freely programmable (0/4 ... 20 mA with
max. 500 )
27
AO1– M (GND)
PTC/KTY interface
14 PTC+ Positive PTC/KTY input
15
PTC– Negative PTC/KTY input
Serial RS485 interface
29 P+ RS485 A, USS protocol
30
N– RS485 B, USS protocol
Power supply
9 U 24 V Isolated user power supply +24 V with
100 mA
28
U 0 V Isolated user reference voltage
1
+10 V Non-isolated, stabilized 10 V power
supply for I/O – max. 10 mA
2
0 V Power supply reference
© Siemens AG 2008
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 81 82

Comentarios a estos manuales

Sin comentarios