Using the Setup Assistant ION Setup User Guide
Page 76 © 2010 Schneider Electric. All rights reserved.
You can only load framework files containing the full meter configuration onto a meter using ION Setup.
To load partial framework files, you must use the Designer component of ION Enterprise.
Framework (.fwn) files created in PEGASYS software are not supported.
Firmware upgrade lets you upgrade the meter to gain access to new or
enhanced ION modules. When you perform a firmware upgrade, you are
prompted to download the configuration file onto the meter. See your device
documentation and the Upgrading PowerLogic ION Device Firmware technical
note for more information on upgrading your device’s firmware.
Register Edit lets you to view and modify energy register values.
Template Paste options
Some modules are not copied when upgrading firmware, saving to PC or sending
to a meter. The setup registers of the following modules remain intact and must be
configured manually:
Communications modules
Security Option modules
Security User modules
Log Mail modules
The Template Paste Options screen also allows you the option of retaining PT/CT,
Clock/Nameplate settings and Energy Readings.
PT/CT Settings retains your setup registers for Power Meter modules.
Clock Settings retains your setup registers for the clock module.
Nameplate Settings retains your Owner, Tag1 and Tag2 settings.
Energy Readings retains the integrator values from your energy registers.
ITC Settings retains your instrument transformer correction settings.