ION Setup User Guide Adding and Configuring Devices
The types of modules available in an ION meter and the number of each type that
may be used depend on the kind of device. The ION7650, for example, has 50
Data Recorder modules. The ION6200, on the other hand, has none. Refer to the
ION Device Templates Reference, available from the website, for information on
the available modules for specific devices.
ION registers
ION modules can have a number of setup registers and output registers. ION
registers are data storage locations; the module reads data through its input(s),
manipulates the data according to its function and the values in the setup registers,
and writes the result to its output register(s). The output registers might contain
maximum RMS readings for three-phase current or describe the high-speed
digitized data points for 32 cycles of a single-voltage phase.
Module links
An ION meter is customized by linking ION modules. The output registers of a
module can be linked to the input registers of other modules. This allows data to
flow from one module to the next. The setup registers are internal to each module,
so they do not require linking.
Register classes
Not all output registers can serve as inputs for all modules. There are different
classes of registers, each capable of holding different types of information. For
example, numeric registers contain numbers, Boolean registers contain ON or
OFF information and waveform registers contain waveform data. These registers
are described in the ION Reference. To link two ION modules together, the output
registers of the first module must contain information the next module can use.
Creating new ION modules
1. From the left pane (Network Viewer), click the folder for the module type you
want to create.
2. Select Insert > Module (or click on the toolbar).
If there are sufficient resources on the device and available modules of that type,
the new module appears on the right pane.
TIP
To determine the modules available on an ION device, refer to the ION Device Template Reference,
which can be downloaded from the website.
To determine the number of modules of a particular type that are in use, select the folder in the left pane
then hover over it. A message appears stating how many modules of that type are in use and how many
are available (for example, Modules used: 17 of 20 (3 available)).