System Products
Line couplers
14/12
Siemens ET G1 · 10/2008
14
Technical specifications
Type Description
N 140/03
N140/13
N 140/03, N140/13 line/backbone couplers
1)
• For data exchange between two KNX bus lines with telegrams
of up to 64 byte
• For use as line coupler for connecting a line to the main line or
as backbone coupler for connecting a main line to the
backbone line or as repeater for connecting two segments of
the same line, with electrical isolation of the two bus lines
• Loadable filter table for control of the data exchange between
the two bus lines
Additional loadable filter table for telegrams with LTE addressing
• Detection of a communication fault on the lower-level line and
signaling to the higher-level line
3 LEDs for display of availability and receipt of a telegram per line
• Power supply from the main line
• Modular installation devices for mounting on
TH35 EN 60715 mounting rail
N 140/03 line/backbone couplers
With bus connection to the line via contact system for
data rail and to the main line via bus terminal
Width: 1 MW (1 MW = 18 mm)
N 140/13 line/backbone couplers
Bus connection to the line and to the main line via
bus terminal
Width: 2 MW (1 MW = 18 mm)
N 146 N 146 IP routers
2)3)
• For data exchange between two KNX bus lines with telegrams
of up to 64 byte
• For interconnection of bus lines or bus areas over a fast data
network (Ethernet 10BaseT) with Internet protocol (IP)
Can be used as line, area or network gateway (worlds gateway)
• Loadable filter table for control of the data exchange between
the two bus lines
Additional loadable filter table for telegrams with LTE addressing
• Detection of a communication fault on the lower-level line and
signaling to the higher-level line
• For communication between KNX devices and PCs and in
conjunction with a LAN modem for remote access to an
KNX installation
Uses the KNXnet/IP protocol
• Assignment of the network parameters by the installation
engineer using ETS or automatically by a DHCP service in
the network
5 LEDs for indicating that the device is ready-to-run,
KNX communication, IP communication
Electronics powered over an external power supply unit for
12 ... 30 V
• Plug-in terminal block for the connection of an external
power supply unit
Integrated bus coupling units
• Bus connection via bus terminal
Ethernet connection over RJ45 socket
Modular installation devices for mounting on
TH35 EN 60715 mounting rail
Width: 2 MW (1 MW = 18 mm)
1)
As far as the hardware is concerned, there is no difference between line coupler, backbone coupler or repeater. They therefore have the same order number.
The function of the device is set during commissioning with the ETS.
2)
During configuration of the IP interface, the installation engineer should carry out all the necessary settings; the network parameters can be assigned either
by the installation engineer over the ETS or automatically by a DHCP service in the network.
3)
The N 146 IP router can only function smoothly as a line coupler (KNXnet/IP routing) if it is equipped with network components that support IP multicasting.
In particular, network/LAN routers must support or be configured so that they can relay IP multicast datagrams. The IP multicast address 224.0.23.12 is
reserved internationally for KNXnet/IP routing.
For selection and ordering data, see page 14/13.
ET_G1_2009_en.book Seite 12 Freitag, 28. November 2008 9:50 09
© Siemens AG 2008