Devices for Special Applications
Lighting
Light level controls
5/14
Siemens ET G1 · 10/2008
■
Overview
■
Technical specifications
Type
AP 255/11
UP 255/12
N 526/02 UP 258/11 UP 258/21 N 342 AP254/02 GE 252 GE 253 GE 254
UP 255 AP 255
Control
Integrated constant light level control
1-channel 3-channel -- -- -- 1-channel -- -- 1-channel -- 1-channel
Integrated two-step control
1-channel -- -- -- -- 1-channel -- -- 1-channel -- 1-channel
Light level control dependent on
surrounding light
-- -- -- -- -- --
✔
✔
-- -- --
Light sensor
External light -- -- -- -- -- -- --
✔
--
✔
--
Indoor brightness
✔
--
✔ ✔ ✔ ✔
-- --
✔
-- --
Indoor brightness
(indirect lighting)
✔
-- -- -- -- -- -- -- -- --
✔
Transmission of brightness values
over KNX
✔
-- -- --
✔ ✔
--
✔ ✔ ✔ ✔
Type
UP 255/11 AP 255/12 N 526/02 UP 258/11 UP 258/21 N 342 AP254/02 GE 252 GE 253 GE 254
Enclosure data
Design UP AP N UP UP N AP GE GE GE
Modular installation device in oblong design, for
installation in luminaires for fluorescent lamps
-- -- -- -- -- -- --
✔ ✔ ✔
Modular installation devices for mounting on
TH35 EN 60715 mounting rail
-- --
✔
-- --
✔
-- -- -- --
Dimensions
•Height mm 30 30 87 102 110 42 42 42
• Width (1 MW = 18 mm) mm
52 52 6 MW 87 102 1 MW 72 274.5 274.5 274.5
•Depth mm
33 33 60 33 54 28 28 28
Power supply
Electronics powered over bus voltage
✔ ✔
--
✔ ✔
--
✔ ✔ ✔ ✔
Electronics powered over an integrated
power supply unit, supply voltage 230 V AC
-- --
✔
-- --
✔
-- -- -- --
Bus connection
Integrated bus coupling units
✔ ✔ ✔
--
✔ ✔ ✔ ✔ ✔ ✔
Plug onto UP 110 bus coupling unit -- -- --
✔
-- -- -- -- -- --
Plug onto UP 114 bus coupling unit
-- -- --
✔
-- -- -- -- -- --
Bus connection via bus terminal
✔ ✔ ✔
--
✔
--
✔ ✔ ✔ ✔
Bus connection over contact system to data rail -- -- -- -- --
✔
-- -- -- --
For selection and ordering data, see page 5/16.
Type Description
UP 255/11
AP 255/12
UP 255/11 and AP 255/12 brightness controllers
• For measuring the brightness on an illuminated work area
through measurement of the reflected light
• Measuring range 0 ... 2000 lux (with a reflectance of the
illuminated area of approx. 30 %)
• Including two rigid optical fiber rods:
- Parallel light-sensitive surface for mounting surface
- Inclined (45°) light-sensitive surface for mounting surface
• Integrated infrared receiver for calibration of the brightness
measurement over an infrared remote control
• Transmission of the brightness measured value, either in the
event of change and/or cyclically
• Optional two-step dimmer control for lamps that can only be
switched, or constant light level control for lamps that can be
switched and dimmed
• Setpoint can be adjusted either over a parameter or a
communication object
• Starting value of the lighting can be selected when the constant
light level control starts up
• Optionally with dimming of up to 4 further lamp groups
• To the dimming value of the constant light level control or to a
dimming value that differs from the dimming value of the
constant light level control by an offset value, which can be
set per group
• Automatic deactivation of the constant light level control by
manual BRIGHTER/DARKER dimming or dimming to a preset
dimming value
• Configurable behavior in the event of a bus power recovery
UP 255/11
• For mounting in a hollow-wall or flush-mounting box with
∅
58 mm and min. 40 mm mounting depth
• Cover made of white plastic (polystyrene)
• Dimensions (H x W x D): 30 x 52 x 33 mm
AP 255/12
• For ceiling or wall mounting
• Includes surface-mounting enclosure made of white plastic
(polypropylene) with
∅
70 mm and 24 mm in height
• Dimensions (H x W x D): 30 x 72 x 33 mm
ET_G1_2009_en.book Seite 14 Freitag, 28. November 2008 9:50 09