Devices for Special Applications
Heating, Cooling, Ventilation, Air-Conditioning
Electromotive valve actuators for HCVA
7/13
Siemens ET G1 · 10/2008
■
Technical specifications
Type
AP 560H AP 560H02 AP 562
Enclosure data
Dimensions
•Height mm 60 60 82
•Width mm 46 46 50
•Depth mm 47 47 65
Power supply
Bus-powered electronics and drive
✔ ✔ ✔
Bus connection
Integrated bus coupling units
✔ ✔ ✔
Bus connection over permanently fixed
connecting cable
✔ ✔ ✔
Inputs
Pushbutton inputs
For signal input (floating contacts) -- -- 2
Output
Electrothermal actuators (silent)
230 V/50 Hz
-- -- --
Valve position in de-energized state -- -- --
Electromotive actuators
✔ ✔ ✔
Stroke max. mm 4.5 4.5 7.5
Automatic adjustment of travel to the
valve used (valve stroke detection)
✔ ✔ ✔
Length of connecting lead m 1 5 0.8
Mounting on company valves
• Direct -Heimeier --
• With spacer ring -- - Danfoss RA
-Heimeier
-MNG
- Schlösser (3/93 ff.)
- Honeywell
-Braukmann
- Dumser (distribution boards)
- Reich (distribution boards)
-Landis + Gyr
-Oventrop
-Herb
-Onda
• Adapter set
For connection to other valve makes, adapters can be
obtained from Heimeier
--
For selection and ordering data, see page 7/14.
ET_G1_2009_en.book Seite 13 Freitag, 28. November 2008 9:50 09