Devices for Special Applications
Heating, Cooling, Ventilation, Air-Conditioning
Sensors for HCVA
7/3
Siemens ET G1 · 10/2008
7
Technical specifications
Type Description
N 258/02 N 258/02 temperature sensors
For four Pt1000 sensors
For the measurement and transmission of 4 temperatures in the
range -40 ... +150 °C
• For connection of four Pt1000 temperature sensors, each over
an up to 50 m long 2-wire cable
• Configurable smoothing of a measured value through mean
value generation
• Monitoring of a lower and upper limit value for each measured
value, with configurable hysteresis for limit value signals
• Electronics powered over an integrated power supply unit for
230 V AC
Green LED for displaying ready-to-run status
Integrated bus coupling units
• Bus connection over bus terminal and contact system to
data rail
Modular installation devices for mounting on
TH35 EN 60715 mounting rail
Width: 4 MW (1 MW = 18 mm)
N 670 Universal N 670 I/O modules
2 x universal I/O, 2 inputs Pt1000, 2 relay outputs 230 V AC, 10 A
• 2 universal inputs/outputs, each adjustable as
- Analog input 0 V ... 10 V DC
- Analog output 0 V ... 10 V DC
- Binary input for 10 V DC
- Binary output for 10 V DC
• Analog input with limit value monitoring and signaling,
with adjustable limit values and hysteresis
• Analog output with adjustable lower and upper limit of the
output voltage with adjustable voltage value in the event of
bus voltage failure and recovery
• Binary input with pulse edge evaluation
• Binary output with adjustable switching position in the event of
bus voltage failure and recovery
2 inputs for the connection of temperature sensors with Pt1000
measured element for temperature measurement in the range
-25 °C ... +45 °C, with limit value monitoring and signaling,
with adjustable limit values and hysteresis
2 binary outputs, relay contacts rated for 230 V AC,
10 A at p.f. = 1, with
- Configurable actuated position (NO contact/NC contact)
- Positively driven operation
- Configurable switching position in the event of
bus voltage failure and recovery
Electronics powered over an external power supply unit for
24 V AC/DC
Integrated bus coupling units
• Bus connection over bus terminal and contact system to
data rail
Modular installation devices for mounting on
TH35 EN 60715 mounting rail
Width: 4 MW (1 MW = 18 mm)
AP 254/02 AP 254/02 dual sensors
Brightness measurement, temperature measurement,
sun protection control, lighting control
For the detection and transmission of brightness and
temperature, temperature measuring range -25 °C ... +55 °C,
brightness measuring range 1 lux ... 100 kLux,
horizontal sensing angle -60° ... +60°, vertical -35° ... +66.5°
• For the control of switch, dimming and shutter/blind actuators,
depending on the ambient luminosity and/or ambient
temperature
• One sun protection channel for the automatic control of
sun protection equipment, with
- Starting and stopping of automation over an object or a dusk
threshold
- Up to three brightness thresholds for determining the height
and position of the shutters/blinds or roller shutters
- Optional teach-in of dusk thresholds and brightness
thresholds over a teach-in facility
- Locking object for the temporary deactivation of the
sun protection channel function
Up to four universal channels for the control of switch, dimming
and shutter/blind actuators, depending on ambient luminosity
and/or temperature. Optionally available with:
- Threshold switches for brightness
- Threshold switches for temperature
- Threshold switches with logical combination of brightness
and temperature
- Optional teach-in of brightness threshold for each
universal channel over an associated teach-in facility
- Deactivation option for each universal channel over an
associated locking object (1 bit)
- Optional second object for transmission of a second
telegram on fulfillment of threshold conditions
Electronics powered over bus voltage
Integrated bus coupling units
• Bus connection via bus terminal
• Surface mounting
Degree of protection, IP54
For selection and ordering data, see page 7/4.