Devices for Special Applications
Lighting
Light level controls
5/15
Siemens ET G1 · 10/2008
N 526/02 N 526/02 switch/dimming actuators, triple
3 x 230 V AC, 50/60 Hz, 6 A, with integrated constant light
level control
• LED for status indication per input
• LED for status indication per output
• LED for operation/status indication
• Pushbuttons for local operation on the device
• 3 control outputs 1 ... 10 V DC
• Max. 50 ECG per output (Osram Dynamik 58 W)
• 3 floating relay contacts
• Rated contact voltage, 230 V AC
• Rated contact current 6 A
• 3 inputs for AP 255/UP 255 brightness sensors,
max. 100 m cable length, unshielded, untwisted
• Switching ON/OFF
• Configurable starting value
• ON/OFF switching possible over BRIGHTER/DARKER dimming
• BRIGHTER/DARKER dimming
• Adjustable dimming time
• Set 8-bit value
• Integrated constant light level control per output
(outputs are master/slave-capable)
• Configurable behavior in the event of a
bus power failure/recovery
• Send switching and dimming status
• Night mode (lighting for cleaning)
Accessories
AP 255
UP 255
AP 255/UP 255 indoor brightness sensors
For N 526/02 switch/dimming actuators
• For measuring the brightness on an illuminated area through
measurement of the reflected light
• Measuring range: 0 ... 1500 lux (with a reflectance of the
illuminated area of approx. 30 %)
• For direct connection to N 526/02 switch/dimming
actuators over a 3-wired cable of up to 100 m in length,
which also serves to power the sensor electronics
• Plug-in low-voltage terminal for connection of the cable to
N526/02
• Including two rigid optical fiber rods:
- Parallel light-sensitive surface for mounting surface
- Inclined (45°) light-sensitive surface for mounting surface
UP 255 indoor brightness sensor
• For mounting in a hollow-wall or flush-mounting box
with
∅
58 mm and min. 40 mm mounting depth
• Cover made of white plastic (polystyrene)
• Dimensions (H x W x D): 30 x 52 x 33 mm
AP 255 indoor brightness sensor
• For ceiling or wall mounting
• Includes surface-mounting enclosure made of white plastic
(polypropylene) with
∅
70 mm and 24 mm in height
• Dimensions (H x W x D): 30 x 72 x 33 mm
N 342 N 342 light level control modules
• Ten mutually independent light control functions that control the
indoor lighting depending on the outdoor brightness
• Shared current outdoor light intensity value for all 10 light
control functions, with light intensity measured by an outdoor
brightness sensor and sent to a N 342
• Separate brightness curve per light control function
•
With configuration option per light control function as continuous
dimming control for the detection and transmission of dimming
commands to dimming or switch/dimming actuators or as
2-step control with hysteresis for detection and transmission of
ON/OFF switch commands to switch actuators
• Automatic adaptation (shifting) of the respective brightness
curve to the desired new indoor brightness when the dimming
value is manually changed (e.g. using a bus pushbutton) and
restoration of the original curve when the lighting is switched off
UP 258/11 UP 258/11 presence detectors
With brightness sensor
• Degree of protection IP20
•Motion
•Presence
• Range on either side: 5.5 m
• Horizontal sensing angle: 360°
• Vertical sensing angle: 120°
• Measuring range:
100 ... 1600 lux (standard)
25 ... 200 lux (expanded)
• For measuring indoor brightness
• Transmission of sensor values over bus
UP 258/21 UP 258/21 presence detectors
With constant light level control
• For surface mounting
• Degree of protection IP20
•Motion
•Presence
• Horizontal sensing angle: 360°
• Vertical sensing angle: 120°
• Range on either side: 4 m
• Brightness measuring range 10 ... 1500 lux
• For measuring indoor brightness
• Transmission of sensor values over bus
Accessories
AP 258E AP 258E surface-mounting enclosures
UP 258/21 presence detectors
• For fixing the presence detector as a surface mounting device
• Dimensions (H x W x D): 102 x 102 x 46 mm
Type Description
ET_G1_2009_en.book Seite 15 Freitag, 28. November 2008 9:50 09