Commissioning
5.2 Series Commissioning
Control Units CU240S
54 Operating Instructions, 10/2007, A5E00766042B AC
Automatic download
An automatic download needs a MMC to be performed. It is not possible to perform an
automatic download from a PC or from the BOP.
The automatic download runs as follows according to the settings in P8458 after power cycle
or a after a swap (see "Start-up behavior" in this section).
Table 5-2 P8458 settings after an automatic parameter download from MMC
P8458 setting in CU
EEPROM
P8458 setting on MMC P8458 setting after
start-up
Remark
0 0 0
0 1 0
0 2 2
Only possible in case of
swap
1 0 0 ---
1 1 0 ---
1 2 2 ---
2 0 0 ---
2 1 0 ---
2 2 2 ---
Contrary to a manual download even the fail-safe parameters are downloaded with an
automatic download.
Note
Manual and automatic download
With a manual download all necessary parameters excluding the fail-safe parameters (only
with Cus with fail-safe functions) are downloaded into the inverter. A detailed description is
given in "Series Commissioning" in the commissioning section.
With an automatic download even the fail-safe parameters are downloaded into the inverter.
An automatic download can only be performed with an MMC at Start-up or by swapping an
inverter component (CU or PM). A detailed description is given in "Start-up behavior" of this
section.