Siemens CU240S DP Instrucciones de operaciones Pagina 134

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 234
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 133
Communication
6.2 Cyclic Communication
Control Units CU240S
134 Operating Instructions, 10/2007, A5E00766042B AC
6.2.4 Switch over behavior of Communication telegram
Overview
When switching over the communication telegram, a number of paramaters values is
changed simultanously.
The following parameters might be concerned:
P0820/P0821: Select Drive Data Set
P1035: MOP up source
P1036: MOP down source
For details refer to the following table
Notes to the tables:
P0700 =1 => Commands via BOP
P0700 = 2: => Commands via Terminals
P0700 = 4: => Commands via USS on RS232
P0700 = 6: => Commands via Fieldbus,
PROFIBUS: P2090 (control word 1) and P2091 (control word 2)
PROFInet: P8890 (control word 1) and P8891(control word 2)
Table 6-10 Switch over behavior of telegram structures, Part 1
P0922 = 1 → 20
if P0700 =
1 → 350
if P0700 =
1 → 352/354
if P0700 =
1 → 999/353
if P0700 =
1, 2 4 6 1, 2, 4 6 1, 2, 4 6 1, 2, 4 6
P0820 = no change 2013.15 2090.15
8890.15
no change 2091.4
8891.4
no change no change no change no change
P0821 = no change no change no change no change 2091.5
8890.15
no change no change no change no change
P1035 = 19.13 19.13 19.13 no change 2090.13
8890.13
no change 2090.13
8890.13
no change no change
P1036 = 19.14 19.14 19.14 no change 2090.14
8890.14
no change 2090.14
8890.14
no change no change
Vista de pagina 133
1 2 ... 129 130 131 132 133 134 135 136 137 138 139 ... 233 234

Comentarios a estos manuales

Sin comentarios