Communication
6.1 PROFIdrive Profile V4.1
Control Units CU240S
128 Operating Instructions, 10/2007, A5E00766042B AC
Regulation for the parameter range
The bit for parameter page selection functions as follows:
If it is set to 1, an offset of 2000 is applied in the inverter to the parameter number (PNU)
transferred in the parameter channel request before it is passed on.
,1'
DGFEI H
Figure 6-5 IND page index acyclic
,1'
DGFEI H
Figure 6-6 IND page index cyclic
Table 6-4 Regulation for setting the PNU
Page index Bit
Parameter range
a d c b f e 9 8
Hex value + PNU
0000 … 1999 0 0 0 0 0 0 0 0 0x00 0 – 7CF
2000 … 3999 1 0 0 0 0 0 0 0 0x80 0 – 7CF
4000 … 5999 0 0 0 1 0 0 0 0 0x10 0 – 7CF
6000 … 7999 1 0 0 1 0 0 0 0 0x90 0 – 7CF
8000 … 9999 0 0 1 0 0 0 0 0 0x20 0 – 7CF
… … … … … … … … … … …
32.000 … 33.999 0 0 0 0 0 1 0 0 0x04 0 – 7CF
… … … … … … … … … … …
64.000 … 65.999 0 0 0 0 1 0 0 0 0x08 0 – 7CF
Table 6-5 Example coding for parameter no. in PKE and IND for P8820, Index 16
PKE IND
decimal xx 820 32 16
hex xx 334 20 10