Manual – MOVITOOLS® - Connection to SIMATIC S7 via MPI
3
Configuration of drives via MPI
Configuration of SIMATIC S7
3 Configuration of SIMATIC S7
The
FC_MoviTools
function and two data blocks must be added to the STEP7 project
to operate MOVITOOLS
®
via the SIMATIC S7 MPI. The SEW-EURODRIVE scope of
delivery includes two S7 projects for SIMATIC CPUs with and without DPV1 firmware.
The following sections are a description of configuration and programming.
3.1 Configuration of drives via MPI
Configure the SEW-EURODRIVE drives as usual in the STEP7 hardware configuration.
Note the following instructions for trouble-free operation of MOVITOOLS
®
via MPI:
Use the same periphery addresses for the input and output ranges when planning
the parameter channel.
Assign only PROFIBUS addresses in the range 3 ... 99 to SEW-EURODRIVE drives.
Use the hardware configurations of SEW-EURODRIVE drives in STEP7 as well as
the device configurations in the GSD file. Make sure you plan the parameter channel
with 4 words and maintain consistency over the entire length when configuring a
drive from SEW-EURODRIVE.
If you have distributed the SEW-EURODRIVE drives to several PROFIBUS master
systems, these drives may not have identical PROFIBUS addresses. You cannot use
MOVITOOLS
®
to set the drive parameters in case of identical PROFIBUS address-
es. Make sure that all SEW-EURODRIVE drives on one SIMATIC S7 CPU have dif-
ferent PROFIBUS addresses.
You should select DPV1 mode (if this mode is supported by the drives and your SI-
MATIC S7 CPU) so that you will be able to use all MOVITOOLS
®
applications during
operation via MPI.
3.2 Copying data blocks
Operation of MOVITOOLS
®
requires a communication data block (CDB) as well as a
hardware data block (HDB). Copy these data blocks from the provided SEW-EURO-
DRIVE STEP7 project to your project because both blocks have a version string in the
header.
Communication
data block
The communication data block (CDB) serves as a local data block for the SEW function
FC_MoviTools
. Make sure that there is no access to this data block from your S7 appli-
cation. Manual entries are not necessary for this data block.
Hardware data
block
The hardware data block (HDB) contains the list of SEW-EURODRIVE drive inverters
that can be accessed via MOVITOOLS
®
and that are connected to the lower-level
PROFIBUS systems. Adjust this hardware data block to match the hardware configura-
tion of your project. The hardware data block is read in via the MOVITOOLS
®
MPI to
determine the list of connected drive inverters from SEW-EURODRIVE.
The HDB and CDB data blocks are to occur only once in the SIMATIC S7 program.
MOVITOOLS
®
will not be started via MPI if copies of these blocks with the same version
string in the header are saved with a different data block number in the SIMATIC S7.
You can choose any number between DB1 and DB254 for both data blocks.
MOVITOOLS
®
does not recognize any data block numbers outside this range.