Ratings,Stationary Drawouts and PowerConnectors
UL Symmetrical RMS Amperes Interrupting Ratings (kA)
Optional Ratings and Breaker Frame Size
Application Voltages 1200A 2000A 3200A 5000A
Alternate A. I. R. (kA): Blue Label “SBA”
@ 240V AC 65 85 N/A N/A
@ 480V AC 65 65 N/A N/A
@ 600V AC 42 50 N/A N/A
Standard A. I. R. (kA): Black Label “SBS”
@ 240V AC 100 100 150 150
@ 480V AC 100 100 100 100
@ 600V AC 50 65 85 85
High A. I. R. (kA): Red Label “SBH”
@ 240V AC N/A 200 200 200
@ 480V AC N/A 150 150 150
@ 600V AC N/A 100 100 100
Short Time Rating
1
(kA), T = 0.5 Sec. 25 35 50 65
IEC 947-2 Rating - Standard SBS
AC Breaker Frame Size
Voltages 1200A 2000A 3200A 5000A
Icu 100kA 100kA 100kA 100kA
415 Ics 100kA 100kA 100kA 100kA
Icw 25kA 35kA 50kA 65kA
Icu 65kA 65kA 65kA 65kA
690 Ics 65kA 65kA 65kA 65kA
Icw 25kA 35kA 50kA 65kA
Interrupting
Ratings
Symmetrical
RMS Amperes
50/60 Hz.
Table B: Stationary Drawout Element
Includes only the drawout mechanism or cell which must be installed in the switchboard. The appropriate Drawout Breaker Element should be
selected from Table A.
SBA
SBS
SBH
Stationary Drawout Element
Breaker Frame Vertical Bus
2
Horiz. Bus
2
Frame Ampere Catalog Catalog
Size Rating Number Number
1200 400 SBA08DFV SBA08DFH
1200 800 SBA08DFV SBA08DFH
1200 1200 SBA12DFV SBA12DFH
2000 1200 SBA20DFV SBA20DFH
2000 1600 SBA20DFV SBA20DFH
2000 2000 SBA20DFV SBA20DFH
1200 400 SBS08DFV SBS08DFH
1200 800 SBS08DFV SBS08DFH
1200 1200 SBS12DFV SBS12DFH
2000 1200 SBS20DFV SBS20DFH
2000 1600 SBS20DFV SBS20DFH
2000 2000 SBS20DFV SBS20DFH
3200 2500 SBS32DFV
3200 3200 SBS32DFV
5000 2500 SBS40DFV
5000 3200 SBS40DFV
5000 4000 SBS40DFV
5000 5000 SBS50DFV
2000 800 SBH20DFV
2000 1200 SBH20DFV
2000 1600 SBH20DFV
2000 2000 SBH20DFV
3200 2500 SBH32DFV
3200 3200 SBH32DFV
5000 2500 SBH40DFV
5000 3200 SBH40DFV
5000 4000 SBH40DFV
5000 5000 SBH50DFV
1
Withstand ratings are equal to the short time ratings.
2 Primary bus connector orientation. Must match drawout breaker selected from Table A. 1200 and 2000 ampere frame bus connections may be
oriented vertically or horizontally.
7
Vista de pagina 7