11
SB-ECTrip Unit Accessories
Catalog Number Input Voltage
SBEPS 120 VAC
SBEPS24 24 VDC and 48 VDC
Table F: SB-EC External Power Supply
Table G: SB-EC Potential Transformer (PT) Modules
Required SB-EC Trip Unit Accessories
Note: One power supply can power up to three trip units. Max wire length
between trip unit and power supply is 50 feet.
Note: One PT module can power up to three trip units when the line side bus is
common. Max wire length between PT module and each trip unit is 50 feet.
Table H: SB-EC Wire Kit Accessories
Note: Select one wire kit per trip unit according to mounting configuration.
Factory wired.
Note: This accessory is required only for remote breaker open/close operation
via R5232 or RS485 communications. This accessory cannot be supplied in
addition to the Bell Alarm or Display Module Relay. This accessory requires
the Shunt Trip and Electric Motor Operator Accessories’ control voltage to be
the same as this accessory.
Note: Field installable by Siemens Field Service personnel only. This accessory
for retrofitting existing SB Breaker installations with SB-EC Trip Units. Trip Unit
and required accessories should be ordered separately.
Catalog Number Frame Size Description
SBECDAK 1200, Drawout
SBECFAK 2000 Fixed Mount
SB3ECDAK
3200
Drawout
SB3ECFAK Fixed Mount
SB4ECDAK Drawout
SB4ECFAK
5000
Fixed Mount
Table J: SB-EC Remote Open/Close and Alarm Relay Accessory
Catalog System Additional
Number Voltage Relay Contact
SBECDMR120 Alarm Contact
SBECBA120
120 VAC
Bell Alarm
SBECDMR24
24 VDC
Alarm Contact
SBECBA24 Bell Alarm
SBECDMR48
48 VDC
Alarm Contact
SBECBA48 Bell Alarm
SBECDMR125
125 VDC
Alarm Contact
SBECBA125 Bell Alarm
Additional SB-EC Trip Unit Accessories
All other SB Breaker Internal and External Accessories may be
used with the SB-EC Trip Unit except the Remote Indicator Panel
(type SBRIP), Auxiliary Power Module (type SBAPM), Ground
Fault Monitor, (type SBGFM), and Plug-in Display Module
(type SBDM).
Frame Size Catalog Number
1200, 2000, 3200 SBECAKT
5000 SB4ECAKT
Table K: SB-EC Trip Unit Retrofit Kit
Communications
Open-protocol communications allows all SB Trip Units to be inte-
grated into Siemens supervisory software (WinPM™ V4.0) and
other popular third party energy monitoring networks. Protocol
Converters are available from the Siemens ACCESS Group for
connection to a variety of open and proprietary automation proto-
cols, including Profibus DP, LonWorks, the Siemens S7 PLC, and
many other third party PLCs. Refer to Bulletin IPIM-2211A for
additional information. EIA-232 communications is also available
for local PC communication and trip unit configuration via Siemens
SBWin™ software.
No additional accessory devices are required for integration of
the SB-EC Trip Unit into the ACCESS™ Communication System.
A Multiplexer/Translator (Catalog No. MTZ) and Expansion Plug
communication components are always required for Zone Selec-
tive Interlocking and must be ordered separately. Refer to page
13-14 for additional information.
Remote Automatic Operation
Remote, automatic open and close operation of the breaker
is possible via the SB-EC Trip Unit’s EIA-485 or EIA-232 com-
munication ports or a hard-wire input. Remote operation using
a communication port requires a protocol converter or Siemens
WinPM™ V4.0 software for EIA-485 Networked Communica-
tions or SBWin™ software for EIA-232 PC Communications for
the following required accessories. The Shunt Trip and Remote
Open/Close Relay accessories are required for the remote open
function, and the Electrical Operator accessory is required in
addition for both remote open and close operations.
Remote, automatic operation via a hard-wire input uses the
following accessories with optional control voltages available.
Only the Shunt Trip Accessory is necessary for the remote open
function, and the Electrical Operator is additionally required for
both remote open and close operations.
Catalog Number Systems Voltage (VAC)
SBPTM240 240
SBPTM480 480
SBPTM600 600