General Information
Compact Size
For space-limited installations, the 1200A and 2000A frames offer
a common width of 15 1/2 inches, a common depth of only 12 1/8
inches, a common mounting footprint, and common bus center
lines. This compact, shallow depth (even with drawout breakers)
permits stacking of six 800A or 1200A breakers or four 2000A
breakers in a standard switchboard. This packaging is made
possible by the insulated-encased construction and thermal
performance of the SB breaker. Even when operated at 100%
of the frame rating, no additional ventilation is required for the
1200A and 2000A frames.
When operated at 100% of the frame rating, 4000A and 5000A
frames require 66 in
2
of ventilation space in the top and bottom
of the front cover. The 3200A frames require no additional ven-
tilation. Detailed outline drawings of the breakers and drawout
elements are included in the Outline Dimensions section starting
on page 22.
Bus Spacing and Connections
Specific installation features of SB breakers include common pole
spacings and vertical connections. These pole spacings allow for
a standard bus connection as specified in UL 891. Detailed outline
drawings are contained in the Outline Dimensions section starting
on page 22.
Two-Step Stored Energy Mechanism
A two-step stored energy mechanism is used to close and
open the breaker. Energy is initially stored in the main springs
of the stored energy mechanism. When the breaker is closed,
spring energy is consumed and sufficient energy is retained in
the breaker to perform the tripping function.The stored energy
mechanism may be charged manually (standard) or electrically
(optional). Pushbutton controls allow for easy opening and closing.
Color-coded indicators clearly display the opened or closed status
of the circuit breaker and charged or discharged status of the
stored energy mechanism. Once the breaker is closed, the mech-
anism can be recharged. The breaker is now prepared for a rapid
open-close or open-close-open operation.
Centralized Controls
The manual charging handle, pushbutton control switches, and
color-coded indicators are grouped in the central escutcheon on
the front cover. The U-shaped construction of the charging handle
provides for a firm grip regardless of the position of the breaker
in the switchboard. For safety, the charging handle and push-to-
close pushbutton are interlocked. This interlock prevents the
breaker from being closed unless the charging handle is in the
stowed position, the position to which it will automatically return
when it is released. The interlock also prevents the breaker from
being manually changed if the close button is depressed.
0 1 2 3 4 5 6
0 ✓✓✓
1 ✓✓✓
2 ✓ ✓
1
3 ✓✓
4
1200A Size Frames
2000A Size Frames
Possible Number of Frames in a 90-inch Switchboard.
1
Example: Three 1200A and two 2000A breaker combination is possible.
Main Stored Energy Spring in Front Compartment
Centralized Controls and Color-Coded Indicators
3