Alternate cable lengths available by special order. Contact your local sales office for details.
Multiplexer/Translator (MT)
The Multiplexer/Translator is a mini-computer that collects data
from different components integrated into the ACCESS communi-
cations system and transmits the data to other components in the
system. The Multiplexer/Translator can receive data from as many
as eight (8) field devices and multiple Multiplexer/ Translators can
be connected together as required via MTC cables.
A Multiplexer/Translator (MTZ) and Expansion Plug are required
whenever Zone Selective Interlocking is specified for any trip unit.
A Multiplexer/Translator (MTA) and Expansion Plug are required for
the Type “TL” trip unit when full ACCESS™ communications is spec-
ified. The MTA also has Zone Selective Interlocking capability. Refer
to Bulletin IPIM-2211A for additional information.
Catalog Number MTZ
MT For Zone Selective Interlocking (ZSI) Only
Catalog Number MTA
MT Full Access Communications Plus Zone Selective
Interlocking
Always required for Zone Interlocking.
Required for Type “TL” Trip Unit when ACCESS Communications and Zone
Selective Interlocking (ZSI) is specified.
External Accessories and ACCESS
Communications
Local Display Unit (LDU)
The LDU provides a central viewing point for up to 32 ACCESS
devices, including SB Trip Units, Sensitrip MCCB Trip Units and
4300 Power Meters. The display features a 4x20 backlit LCD
read-out of real-time metering and configuration data. The device
is menu driven and features a “self learn” mode to automatically
configure itself for the ACCESS devices on the network. Panel-
mountable for switchboard applications, with simple 2-wire
RS-485 communication connectivity.
Description Catalog Number
Local Display Unit
1
LDU-100
19
Catalog Number Description
1
MTCSB08 Telephone cable, 8’, used between Expansion Plug and Multiplexer/Translator
MTCSB15 Telephone cable, 15’, used between Expansion Plug and Multiplexer/Translator
MTCSB25 Telephone cable, 25’, used between Expansion Plug and Multiplexer/Translator
MTC08 Telephone cable, 8’ used between multiple Multiplexer/Translators
MTC15 Telephone cable, 15’ used between multiple Multiplexer/Translators
MTC25 Telephone cable, 25’ used between multiple Multiplexer/Translators
Cables and Connectors
ACCESS communications system components can be connected together using standard, commercially available cables and connectors.
Refer to Information and Instruction Guide IPIM-2211A for specific cable and connector specifications and requirements. Cables and con-
nectors can be ordered per the table below. Select longer length when unsure of mounting configuration.
Catalog Number SBAPM
Expansion Plug
The Expansion Plug is an electronic interface and isolation module
necessary to integrate a breaker into an ACCESS System. One
Expansion Plug is required for each circuit breaker in the system
and is used to interface SB Breaker trip units to the Multiplex/
Translator. The Expansion Plug is always
necessary for zone inter-
locking or full ACCESS communications for the Type TL trip unit.
An Expansion Plug is not required for ACCESS communications
using the SB-EC Trip Unit but is required for zone interlocking.
Factory or Siemens Field Service field installable only.
Type “TL” Trip Unit Auxiliary Power Module
A device used to bring power into the SB breaker type “TL”
electronic trip unit only so that the trip unit can be tested via the
integral testing functions when the breaker is withdrawn from the
Stationery Drawout Element. It is required to trip the breaker’s
shunt trip when no primary power is applied to the breaker or
when “bench testing” the electronic trip unit.
Communication and Zone Selective Interlocking Component
Selection Guide
Required Accessory Trip Unit and Application
“TL” for Access
SB-EC “TL” Communications
for ZSI
2
for ZSI and/or ZSI
3
MTZ
3
XX
MTA
3
X
EPSBxxMK
4
XX
MTCSBxxCable
5
XX X
1
One EP required per Trip Unit when specified.
2
No additional components are required for the SB-EC Trip Unit to communi-
cate over the ACCESS Bus.
3
The MTA can also accommodate an SB-EC Trip Unit for ZSI functionality.
4
Replace xx in catalog number with 08, 15 or 25 for required cable length of
8’, 15’ or 25’ respectively. One cable required per EP when specified.
5
One MTA or MTZ can accommodate eight trip units. Multiple MT’s can be
connected via MTC cables.
Type of 800-2000A 3200, 4000-5000A
Mounting Cat. No.
1
Cat. No.
1
Fixed EPSBFMK EPSB4FMK
Drawout EPSBDMK EPSB4DMK
1
Available 3/99.