Table N: Electrical Operators
Electric Operators function to automatically charge the SB break-
er’s stored energy mechanism. Each operator includes a Remote
Closing Solenoid for closing the breaker from a remote location
and an electronic controller which provides anti-pump protection
and remote charging capability and indication. The Closing Coil
Interlock (CCX) option allows the customer to block the operation
of the closing coil by adding an external electrical contact/interlock
in the breaker’s closing coil circuit. A Shunt Trip or Under Voltage
Release should be ordered and priced separately for remote open-
ing of the breaker. UL listed for field installation.
Electrical Operators With Electric Close
Electric Operators with Local Electric Close provide an electric
close pushbutton on the breaker escutcheon that can be electri-
cally interlocked with an external control circuit. The Closing Coil
Interlock Option is also available on operators equipped with Local
Electric Close. Factory installation only. Note that “Push to Close”
and “Push to Open” pushbutton operators are provided on the
breaker escutcheon as standard.
Voltage
Frame Catalog Catalog Number
Sizes AC DC Number w/CCX Option
120 — SBEO120LEC SBEO120LECCCX
1200
— 24 SBEO24LEC SBEO24LECCCX
2000
—48SBEO48LEC SBEO48LECCCX
3200
— 125 SBEO125LEC SBEO125LECCCX
120 — SB4EO120LEC SB4EO120LECCCX
5000
—24SB4EO24LEC SB4EO24LECCCX
—48SB4EO48LEC SB4EO48LECCCX
— 125 SB4EO125LEC SB4EO125LECCCX
Table P: Secondary Contact Blocks
Contact blocks are required for secondary control wiring. Sliding
Secondary Disconnects are required on drawout mounted break-
ers, and Control Terminal Blocks are required for fixed mounted
breakers. The appropriate number and location of contact blocks
should be selected from the table below based on the features
and accessories ordered on each circuit breaker. Control Terminal
Blocks require a mounting bracket as shown below. All Siding
Secondary Disconnects or Control Terminal Blocks should be
priced separately.
Accessory
CCX Bell Alarm
1
SB-EC
Option or Display Trip Unit Auxiliary Switches
or Zone Module Relay External
Contact Remote Under- Remote
1
Interlock or Remote Power 1Aand1B 4Aand4B
2
Block Electric Closing Shunt voltage Neutral Indication and Open/Close Supply and 2Aand2B 5Aand5B
2
Position Operator Solenoid Trip Release Sensor Panel ACCESS Relay PT Module 3Aand3B 6Aand6B
23
LT X X X X X
LB X X X
RT XX X
RB X
Contact Position Catalog Number
LT SBSDLT
LB SBSDLB
RT SBSDRT
RB SBSDRB
Sliding Secondary Disconnects
Contact Position Catalog Number
LT SBTBLT
LB SBTBLB
RT SBTBRT
RB SBTBRB
Control Terminal Blocks
Mounting Bracket for Terminal Block
For mounting Control Terminal Blocks to fixed mounted breakers.
One bracket required for mounting locations LT and LB and a
separate bracket required for mounting locations RT and RB.
Catalog Number SBTBM
1
Remote Indicator Panel, Bell Alarm, Display Module Relay and Remote
Open/Close Relay are mutually exclusive accessories. Only one may be
used per breaker.
2
4A and 4B, 5A and 5B, 6A and 6B auxiliary switches not available with
SB-EC Trip Unit.
3
6A and 6B auxiliary switches are not available with the Bell Alarm or Alarm
Relay Accessories.
LT RT
RBLB
Secondary Contact Block Locations
Electrical Operators CCX Option
Electrical Operators with
Local Electric Close CCX Option
Voltage
Frame Catalog Catalog Number
Sizes AC DC Number w/CCX Option
120 — SBEO120 SBEO120CCX
1200
— 24 SBEO24 SBEO24CCX
2000
—48SBEO48 SBEO48CCX
3200
— 125 SBEO125 SBEO125CCX
120 — SB4EO120 SB4EO120CCX
—24SB4EO24 SB4EO24CCX
5000
—48SB4EO48 SB4EO48CCX
— 125 SB4EO125 SB4EO125CCX