Appendix C: Device Data Format
94 Siemens Energy & Automation, Inc.
General Status Word 6:
1
18 Bit Contents
14–15 Not Used
13 59-Overvoltage protection is ACTIVE (Valid)
12 59-Overvoltage protection is ACTIVE (Status)
11 59-Overvoltage protection switched OFF (Valid)
10 59-Overvoltage protection switched OFF (Status)
9 27-Undervoltage protection is ACTIVE (Valid)
8 27-Undervoltage protection is ACTIVE (Status)
7 27-Undervoltage prot. switched OFF (Valid)
6 27-Undervoltage prot. switched OFF (Status)
5 >27-2 BLOCK UV protection second step (Valid)
4 >27-2 BLOCK UV protection second step (Status)
3 >27-1 BLOCK UV protection first step (Valid)
2 >27-1 BLOCK UV protection first step (Status)
1 46-Negative seq. is ACTIVE (Valid)
0 46-Negative seq. is ACTIVE (Status)
Number of Last Fault 19 0…32767, 0 = no faults
Fault Date/Time (ms) 20 0…59999 (ms )
Fault Date/Time (h/m) 21 High byte: HH (0…23), Low byte: MM (0…59)
Fault Date/Time (m/d) 22 High byte: MM (1…12); Low byte: DD (1…31)
Fault Date/Time (y) 23 Year: YY (00…99)
Interrupted current:
Phase L1 (I/I
n
)
24 ms since fault (-1 = no occurrence)
Interrupted current:
Phase L1 (I/I
n
)
25 Low word
Interrupted current:
Phase L1 (I/I
n
)
26 High word
Interrupted current:
Phase L2 (I/I
n
)
27 ms since fault (-1 = no occurrence)
Interrupted current:
Phase L2 (I/I
n
)
28 Low word
Interrupted current:
Phase L2 (I/I
n
)
29 High word
Interrupted current:
Phase L3 (I/I
n
)
30 ms since fault (-1 = no occurrence)
Interrupted current:
Phase L3 (I/I
n
)
31 Low word
Interrupted current:
Phase L3 (I/I
n
)
32 High word
Flt Loc.: Secondary react. to
fault
33 ms since fault (-1 = no fault)
Flt Loc.: Secondary react. to
fault
34 Low word
Flt Loc.: Secondary react. to
fault
35 High word
Fault in the power system 36 ms since fault (-1 = no fault)
General Trip of Device 37 ms since fault (-1 = no occurrence)
50BF-Breaker Fail TRIP 38 ms since fault (-1 = no occurrence)
O/C fault detection phase 1 39 ms since fault (-1 = no occurrence)
O/C fault detection phase 2 40 ms since fault (-1 = no occurrence)
O/C fault detection phase 3 41 ms since fault (-1 = no occurrence)
O/C fault detection earth 42 ms since fault (-1 = no occurrence)
Real-Time Device Data Stored in PLC (7SJ512) (Continued)
Function Register Location in
PLC Block
Range or Contents