Appendix C: Device Data Format
104 Siemens Energy & Automation, Inc.
O/C Fault Detection E only 43 ms since fault (-1 = no occurrence)
O/C protection I>> phase Trip 44 ms since fault (-1 = no occurrence)
O/C protection I> phase Trip 45 ms since fault (-1 = no occurrence)
O/C protection Ip phase Trip 46 ms since fault (-1 = no occurrence)
O/C protection IE>> earth Trip 47 ms since fault (-1 = no occurrence)
O/C protection IE> earth Trip 48 ms since fault (-1 = no occurrence)
O/C protection IEp earth Trip 49 ms since fault (-1 = no occurrence)
AR: Close command from
auto-reclose
50 ms since fault (-1 = no occurrence)
AR: Definitive trip 51 ms since fault (-1 = no occurrence)
Neg. seq. I. (I2) prot.: Trip 52 ms since fault (-1 = no occurrence)
O/C protection I>>> phase trip 53 ms since fault (-1 = no occurrence)
Supervision of starting time
trip
54 ms since fault (-1 = no occurrence)
CT Primary 55 0-50000
CT Secondary 56 1 or 5
Reserved 57-60 For Future Expansion
1. Status information for each parameter is transmitted in two bits. The status bit indicates status (true = 1, false = 0) for the parameter
and the valid bit indicates that the device has successfully updated the value in the status bit (true = 1, false = 0).
Device Command Data Retrieved From PLC (7SJ600)
First Command Word (Command Word) Additional Command Words (Data or Value)
0 = No command Unused
1 = Time Sync 2nd Word: Time [ms] - (0-59999)
3rd Word: Time [h/m] - high byte: HH (1-24), low byte: MM (0-59)
4th Word: Date [m/d] - high byte: MM (1-12), low byte: DD (1-31)
5th Word: Date [y] - YY (00-99)
2 = Reset LEDs Unused
Real-Time Device Data Stored in PLC (7SJ600) (Continued)
Function Register Location in
PLC Block
Range or Contents