Appendix C: Device Data Format
Siemens Energy & Automation, Inc. 99
Interrupted current:
Phase L3 (I/I
n
)
36 Low word
Interrupted current:
Phase L3 (I/I
n
)
37 High word
Fault Reactance, Ohm sec. 38 ms since fault (-1 = no occurrence)
Fault Reactance, Ohm sec. 39 Low word
Fault Reactance, Ohm sec. 40 High word
Distance to fault in km 41 ms since fault (-1 = no occurrence)
Distance to fault in km 42 Low word
Distance to fault in km 43 High word
Distance to fault in miles 44 ms since fault (-1 = no occurrence)
Distance to fault in miles 45 Low word
Distance to fault in miles 46 High word
Magnitude of earth current 47 ms since fault (-1 = no occurrence)
Magnitude of earth current 48 Low word
Magnitude of earth current 49 High word
Active component of earth
current
50 ms since fault (-1 = no occurrence)
Active component of earth
current
51 Low word
Active component of earth
current
52 High word
Reactive component of earth
current
53 ms since fault (-1 = no occurrence)
Reactive component of earth
current
54 Low word
Reactive component of earth
current
55 High word
Fault in the power system 56 ms since fault (-1 = no fault)
General Close of Device 57 ms since fault (-1 = no fault)
General Trip of Device 59 ms since fault (-1 = no fault)
General Trip of Protection 59 ms since fault (-1 = no fault)
Trip by displacement voltage
stage
60 ms since fault (-1 = no fault)
Trip by sensitive IEE>> stage 61 ms since fault (-1 = no fault)
Trip by sensitive IEE> stage 62 ms since fault (-1 = no fault)
Trip by sensitive IEEp stage 63 ms since fault (-1 = no fault)
Trip by Breaker Failure
Protection
64 ms since fault (-1 = no fault)
Thermal overload protection
trip
65 ms since fault (-1 = no fault)
O/C fault detection phase 1 66 ms since fault (-1 = no fault)
O/C fault detection phase 2 67 ms since fault (-1 = no fault)
O/C fault detection phase 3 68 ms since fault (-1 = no fault)
O/C fault detection earth 69 ms since fault (-1 = no fault)
O/C Fault Detection L1 only 70 ms since fault (-1 = no fault)
O/C Fault Detection L1-E 71 ms since fault (-1 = no fault)
Real-Time Device Data Stored in PLC (7SJ531) (Continued)
Function Register Location in
PLC Block
Range or Contents