Appendix C: Device Data Format
100 Siemens Energy & Automation, Inc.
O/C Fault Detection L2 only 72 ms since fault (-1 = no fault)
O/C Fault Detection L2-E 73 ms since fault (-1 = no fault)
O/C Fault Detection L1-L2 74 ms since fault (-1 = no fault)
O/C Fault Detection L1-L2-E 75 ms since fault (-1 = no fault)
O/C Fault Detection L3 76 ms since fault (-1 = no fault)
O/C Fault Detection L3-E 77 ms since fault (-1 = no fault)
O/C Fault Detection L1-L3 78 ms since fault (-1 = no fault)
O/C Fault Detection L1-L3-E 79 ms since fault (-1 = no fault)
O/C Fault Detection L2-L3 80 ms since fault (-1 = no fault)
O/C Fault Detection L2-L3-E 81 ms since fault (-1 = no fault)
O/C Fault Detection L1-L2-L3 82 ms since fault (-1 = no fault)
O/C Fault Detection
L1-L2-L3-E
83 ms since fault (-1 = no fault)
O/C Fault Detection E only 84 ms since fault (-1 = no fault)
O/C General Trip Command 85 ms since fault (-1 = no fault)
50HS-Phase high-set element
TRIP
86 ms since fault (-1 = no fault)
50-Phase inst. element TRIP 87 ms since fault (-1 = no fault)
51-Phase time element TRIP 88 ms since fault (-1 = no fault)
50NHS-Ground high-set
element TRIP
89 ms since fault (-1 = no fault)
50N-Ground inst. element
TRIP
90 ms since fault (-1 = no fault)
51N-Ground time element
TRIP
91 ms since fault (-1 = no fault)
67HS-Dir. Phase High-Set TRIP 92 ms since fault (-1 = no fault)
67-Dir. phase inst. element
TRIP
93 ms since fault (-1 = no fault)
67T-Dir. phase time element
TRIP
94 ms since fault (-1 = no fault)
67HS-Dir. Ground High-Set
TRIP
95 ms since fault (-1 = no fault)
67NT-Dir. ground time element
TRIP
96 ms since fault (-1 = no fault)
Dir. O/C fault detection phase
L1
97 ms since fault (-1 = no fault)
Dir. O/C fault detection phase
L2
98 ms since fault (-1 = no fault)
Dir. O/C fault detection phase
L3
99 ms since fault (-1 = no fault)
Dir. O/C fault detection earth 100 ms since fault (-1 = no fault)
Dir. O/C protection TRIP 101 ms since fault (-1 = no fault)
46-Negative seq. protection
TRIP
102 ms since fault (-1 = no fault)
27-1 Undervoltage first step
TRIP
103 ms since fault (-1 = no fault)
27-2 Undervoltage second
step TRIP
104 ms since fault (-1 = no fault)
Real-Time Device Data Stored in PLC (7SJ531) (Continued)
Function Register Location in
PLC Block
Range or Contents