3
General Information
Frame Sizes and Frame Ampere Ratings
SB breakers come in four frame sizes with MAX ratings
ranging from 400A to 5000A. All frames are rated for 100%
continuous operation.
Frame Size and Rating Combinations
Rating Plugs
SB breakers use interchangeable rating plugs. The rating plug
ampere values (I
n
) allows the effective ampere rating of the
breaker to be customized for specific applications. A label on
the front of the breaker identifies the rating plugs that may be
used with that particular breaker.
Available Rating Plugs
Interruption and Short Time Ratings
Three short circuit interruption ratings are available for specific
applications. The interruption ratings and short-time ratings are
given in the following table.
UL 489 Interruption and Short Time Ratings
IEC 947-2 Ratings (SBS Units Only)
The interruption rating of the SB breaker is specified on the
front cover label and is further identified by a color bar at the
top left of the breaker label.
Blue
indicates the alternate or the lowest interrupting cate-
gory (1200–2000A frames). Black indicates the standard inter-
rupting rating. Red indicates the highest available interrupting
rating for the SB breaker.
Overcurrent Protection Configurations
Siemens Electronic Trip Units for SB breakers are available in
seven overcurrent protection configurations to meet specific
protection requirements. Six trip units come equipped with
Adjustable Continuous Current and Long Time Delay func-
tions. Optional protection configurations are:
Protection Configuration Identifier
Long Time/Short Time LS
Long Time/Instantaneous LI
Long Time/Short Time/Instantaneous LSI
Long Time/Short Time/Ground Fault LSG
Long Time/Instantaneous/Ground Fault LIG
Long/Short Time/Instantaneous/Ground Fault LSIG
Fixed Long Time/Instantaneous MLI
The trip unit that may be used with a specific circuit breaker is
identified on the front cover label.
RMS Current Sensing
The trip unit executes the breaker’s overcurrent fault protec-
tion functions. Its adjustment flexibility allows you to accom-
modate load changes and other protection requirements while
still assuring optimum coordination.
A standard trip unit feature is RMS current sensing. RMS
sensing measures the true heating potential of the current
waveform. It allows for more accurate overcurrent protection
and eliminates nuisance tripping due to harmonic distortion of
the current waveform.
Breaker Frame Ampere Size Breaker MAX Ampere Rating
1200 Amperes
(SBA, SBS only)
400, 800, 1200
2000 Amperes 800 (SBH only), 1200, 1600, 2000
3200 Amperes 2500, 3200
5000 Amperes 2500, 3200, 4000, 5000
MAX Rating
Rating Plug Ampere Values (I
n
)
400 200, 225, 250, 300, 350, 400
800 400, 450, 500, 600, 700, 800
1200 600, 700, 800, 1000, 1200
1600 800, 1000, 1200, 1600
2000 1000, 1200, 1600, 2000
2500 1600, 2000, 2500
3200 1600, 2000, 2500, 3000, 3200
4000 2000, 2500, 3000, 3200, 4000
5000 2500, 3000, 3200, 4000, 5000
Breaker Frame Size
1200 2000 3200 5000
Type SBA Alternative Interrupt Rating (Blue Label)
240 V AC
480 V AC
600 V AC
65 kA
65 kA
42 kA
85 kA
65 kA
50kA
——
Type SBS Standard Interrupt Rating (Black Label)
240 V AC
480 V AC
600 V AC
100 kA
100 kA
50 kA
100 kA
100 kA
65 kA
150 kA
100 kA
85 kA
150 kA
100 kA
85 kA
Type SBH High Interrupt Rating (Red Label)
240 V AC
480 V AC
600 V AC
200 kA
150 kA
100 kA
200 kA
150 kA
100 kA
200 kA
150 kA
100 kA
Short Time Rating (t=0.5 seconds)
25 kA 35 kA 50 kA 65 kA
Voltage 50/60 Hz
Frame Sizes
1200 2000 3200 5000
Type SBS Standard Interrupt Rating (Black Label)
415 V AC lcu
lcs
lcw
100 kA
100 kA
25 kA
100 kA
100 kA
35 kA
100 kA
100 kA
50 kA
100 kA
100 kA
65 kA
690 V AC lcu
lcs
lcw
65 kA
65 kA
25 kA
65 kA
65 kA
35 kA
65 kA
65 kA
50 kA
65 kA
65 kA
65 kA