Operating Instructions
Operating the SB Encased Systems Breaker
Discharging the Stored Energy Mechanism Without
Closing the SB Breaker
Discharging the energy in the stored energy mechanism without
closing the breaker creates an abnormally high shock condition
on the breaker.
Avoid this procedure except for safety and/or
emergency reasons.
To discharge the energy, push and hold the
Open pushbutton and then push the Close pushbutton.
On electrically-operated breakers, the electric operator should
be disabled (one way is to remove the fuse) before discharging
the stored energy. Otherwise, the electric operator automati-
cally recharges the springs. To close the breaker, standard clos-
ing-prevention devices require that the following: (1) a trip unit
must be installed in the SB breaker, (2) the stored energy
mechanism must be fully charged, and (3) the charging handle
must be in the stowed position. On drawout constructions,
the release lever must be in the release-engaged position (up
position).
Accessories that inhibit the breaker from being locally closed
are presented in the Accessories section. Included are a clos-
ing-blocking device for use with remotely-operated circuit
breakers, key interlocks, and other locking devices.
Discharging energy from the stored energy mechanism with-
out closing contacts.
Closing the SB Breaker Locally
Before the breaker can be closed, the stored energy mecha-
nism must be fully charged and all of the closing-prevention
devices (and accessories) must be in the noninhibiting state or
position. In this condition, all that is required to close the
breaker is to push the Close pushbutton. When the breaker is
closed the Contacts Closed/Contacts Open indicator will point
to Contacts Closed.
Indicates that the circuit breaker is Closed with the springs in
the Charged position.
Indicates that the circuit breaker is Open with the springs in
the “Discharged” position.
Opening the SB Breaker Locally
To locally open the breaker, push the Open pushbutton. When
the breaker is open, the Contacts Closed/Contacts Open indi-
cator will point to Contacts Open.
Built-in safety devices trip the SB breaker if the trip unit is
removed or the release lever on the drawout mechanism is
depressed. Performing the trip unit integral test in the trip
mode also trips the breaker.