23
Operating Instructions
Manipulating the Moveable Drawout Element
CAUTION
!
Test Position to Connected Position
To rack the moveable drawout element from the Test position
to the Connected position.
1. Push in the directional shift lever. This is the racking-in position.
2. Pull the release lever down to the release-disengaged position.
(Illustrated beneath padlock device.) If the breaker contacts are
closed, pulling the release lever down will trip the breaker.
3. Pump the racking pump handle until the moveable drawout element
is in the Connected position.
4. As soon as the moveable drawout element is racked from the Test
position, the position indicator will display that the moveable
drawout element is in the Connected position. However, the move-
able drawout element will not be completely in the Connected
position until the release lever has automatically returned to the
release-engaged position. Push the side rails back into the stored
position.
To avoid damaging the racking
mechanism, always pull the release lever
before racking the moveable drawout
element.