26
NOTE: Refer to the separate SB Accessories Installation
and Instruction Guide for information on Accessory
Installation and ratings. Refer to the separate SB Trouble
Shooting Guide for trouble-shooting tips.
CAUTION
!
NOTE: Siemens recommends that all accessories be
installed using the instruction information accompanying
the accessory, or by referring to the Accessory Manuals
(IPIS-00105 and IPIS-00106).
1. Before removing the cover check to be sure the circuit breaker main
contacts are open and the closing springs are discharged by first
pushing the open button.
2. Push the close button and then repeat pushing of the open button.
Verify that the status indicators show Spring Discharged and
Contacts Open.
Mechanism can cause severe
injury when cover is removed.
Before removing cover, push open
button, push close button, and then
push open button again.
CAUTION
!
Install all accessories with the breaker
Open and Discharged as shown above.
To avoid injury or damage to equipment,
do not install accessories with breaker
in a Closed or Charged position.
Internal Accessories
Preliminary Installation Procedures