CAUTION
!
Installation of Electronic Trip Unit
The SB breaker has a built-in interlock device that prevents the
breaker from being closed when there is not an installed trip
unit. This same interlock device will trip the breaker when the
trip unit is removed.
1. Remove 8 screws from breaker front cover.
Note: If you are installing a SB-EC Trip Unit, refer to the
Information and Instruction Guide for this device (IPIM-
2208).
To install the trip unit, remove the breaker’s front cover. This is
done by removing the four recessed Phillips head screws in
positions 2, 3, 6, and 7, as well as the four Phillips head screws
in positions 1, 4, 5, and 8, which hold the front cover in place.
NOTE: For more complete information on other standard
and optional features of the electronic trip units, see
Siemens Electronic Trip Units for SB Encased Systems
Breakers Information and Instruction Guide Bulletin IPIM-
2203 and the Sentron Systems Breaker Energy Communi-
cating Trip Unit Information and Instruction Guide
Bulletin IPIM-2208.
2. Lift off front cover.
On trip units with ground fault protection, the ground fault
selection switch on the side of the trip unit must be set to the
appropriate sensing scheme—Residual or Source Ground/Zero
Sequence—before installing the trip unit. The trip unit is preset
at the factory to a residual sensing scheme.
3. Set ground fault selection switch.
Do not attempt to install a trip unit
with the breaker Closed or Charged.
Make certain breaker is Open and
Discharged as shown above. Personal
injury or mechanical damage may occur.
1
8
3
2
6
7
5
4