24
Operating Instructions
Manipulating the Moveable Drawout Element
CAUTION
!
Connected Position to Test Position
To rack the moveable drawout element from the Connected posi-
tion to the Test position, ensure that the SB breaker is open. (If
the breaker is closed and the release lever is moved downward
to the interlock disengaged position, the breaker will trip.)
1. Pull out the directional shift lever. This is the racking-out position.
2. Pull the release lever down to the interlock disengaged position.
(Illustrated beneath the padlock device.) If the breaker contacts are
closed, this action will trip the breaker.
3. Pump the racking pump handle until the moveable drawout element
is in the Test position.
4. When the moveable drawout element reaches the Test position, the
release lever will automatically return to the interlock engaged posi-
tion, the racking pump handle cannot be pumped, and the position
indicator will display that the moveable drawout element is in the
Test position.
To avoid damaging the racking mecha-
nism, always pull the release lever
before racking the moveable drawout
element.