Installation and Set-up
1-19
SIMATIC TI505/TI500 MODNIM User Manual
1.7 Establishing Communications
After
installing and configuring the MODNIM, you should verify that the
module is properly logged into the PLC I/O map.
NOTE:
The PLC I/O map is the first thing to check if the PC GOOD
(PC/NIM COMM GOOD) indicator light is off.
Connect your programming device to the PLC to verify PLC-to-MODNIM
module communication by following these steps.
1.
Access the Configure I/O function menu, then execute Show
.
2.
Execute the Read Base function.
3.
Check all the I/O points on the base that the MODNIM is installed in.
Once you have entered the appropriate commands, the programming
device displays a chart listing all slots on the base and the inputs and
outputs associated with each slot. If a row on the chart is blank, then
the corresponding base slot does not contain a module. Figure 1-14
shows a sample I/O definition chart with a MODNIM installed in Slot 1
of a four
-slot base. (Refer to your TISOFT manual for detailed
instructions.)
I/O
MODULE DEFINITION FOR : CHANNEL 1
BASE 00
Slot Address X Y WX WY Function
I/O
Number of Bit and W
ord I/O
Special
1
2
3
4
.....
.....
.....
.....
0001
0000
0000
0000
.....
.....
.....
.....
00
00
00
00
..
..
..
..
08
00
00
00
..
..
..
..
00
00
00
..
..
..
..
00
00
00
.......
.......
.......
.......
Yes
No
No
No
00 00
Base Number
Displays number
of the current base.
Slot Number
Install
the module into any
available I/O slot in the I/O base.
I/O Address
The module is logged in
as eight outputs (Ys).
SF Module
The MODNIM is logged in as
a Special Function Module.
Figure 1-14 Sample
I/O Definition Chart
V
erifying that the
MODNIM is Logged
into the PLC