11 Alarms 11.90
11.11 Alarm list ACKNOWLEDGE
6146
Decoding DB too short
Cause:
Effect:
Remedy:
DB 80 not set up over full length (DW 0 - 95)
PLC STOP
Set up DB 80 in start-up procedure or input subsequently
6147
Distributed I/Os changed
Cause:
Effect:
Explanation:
Module(s) withdrawn or inserted in cyclic operation
PLC STOP dependent on PLC MD 2003 bit 2
(Intended for installation)
6148
Overtemperature in EU
Cause:
Effect:
Explanation:
Remedy:
Temperature rise in EU, fan breaks down
PLC message 6148 displayed
Monitor on CC interface module
6FX1132-1BA01 module
Check fan
6149
Stop via softkey PG
Cause:
Effect:
Remedy:
Stop command via PG
PLC STOP
PLC Start via PG
POWER ON
11–58 © Siemens AG 1990 All Rights Reserved 6ZB5 410-0DL02
SINUMERIK 810 GA3/820 GA3 (IA)